| | FIRE DEPARTMENT REVIEW ***DENIED**** |
| | ADDRESS:2047 PALM BEACH LAKES BOULEVARD |
| | PERMIT # 12030309 |
| | CONTRACTOR: LEIGHTON MCGINN |
| | PHONE: 561 863-4455 |
| | |
| | 1.) THE SCOPE OF WORK SHALL BE INDICATED ON PLANS. |
| | 2.) DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE |
| | FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA |
| | EDITION OF NFPA 1 AND NFPA 101. |
| | 3.) ALL DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. |
| | 4.) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | 5.) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY |
| | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| | TRAVEL ETC. |
| | 6.) PER FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| | SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | |