| Plan Review Notes For Permit 12030295 |
| Permit Number |
12030295 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-06 10:42:34 | PLANS DENIED | | | 1) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M) | | | PAGE M2-1 ON PLANS TRAINING ROOM. | | | 2) TIPICAL ROOFTOP A/C UNIT DETAIL PAGE M7.1 OF PLANS | | | SHOW DUCT DETECTOR IN RETURN AIR. DUCT DETECTOR MUST | | | BE IN SUPPLY . PER SECTION 606.2.1 SUPPLY AIR SYSTEM. | | | 2007 FBC (M) | | | 3) REFER TO SECTION 606.3 INSTALLATION AND 606.4.1 | | | SUPERVISION. | | | 2007 FBC (M) | | | 4) REFER TO SECTION 601.4 BALANCED RETURN AIR. 2007 FBC | | | (M) | | | 5) REFER TO SECTION 13-409.AB.3.3 SHUTOFF CONTROL'S | | | 2007 ENERGY CODE. | | | 6) RETURN AIR GRILLE SCHEDULE PAGE M6.1 AND RETURN AIR | | | ON PAGE M2-1 | | | DO NOT MATCH. | | | 7) PROVIDE A DETAIL BY THE ENGINEER ON THE CURB TIE | | | DOWN TO THE ROOF. | | | PER SECTION 301.12 WIND RESISTANCE 2007 FBC (M) | | | 8) REFER TO SECTION 301.12 WIND RESISTANCE REFERRING TO | | | WOOD SLEEPERS | | | FOR CONDENSATE. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | | | | | | | |
|