Plan Review Notes
Plan Review Notes For Permit 12030295
Permit Number 12030295
Review Stop M
Sequence Number 1
Notes
Date Text
2012-04-06 10:42:34PLANS DENIED
 1) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M)
 PAGE M2-1 ON PLANS TRAINING ROOM.
 2) TIPICAL ROOFTOP A/C UNIT DETAIL PAGE M7.1 OF PLANS
 SHOW DUCT DETECTOR IN RETURN AIR. DUCT DETECTOR MUST
 BE IN SUPPLY . PER SECTION 606.2.1 SUPPLY AIR SYSTEM.
 2007 FBC (M)
 3) REFER TO SECTION 606.3 INSTALLATION AND 606.4.1
 SUPERVISION.
 2007 FBC (M)
 4) REFER TO SECTION 601.4 BALANCED RETURN AIR. 2007 FBC
 (M)
 5) REFER TO SECTION 13-409.AB.3.3 SHUTOFF CONTROL'S
 2007 ENERGY CODE.
 6) RETURN AIR GRILLE SCHEDULE PAGE M6.1 AND RETURN AIR
 ON PAGE M2-1
 DO NOT MATCH.
 7) PROVIDE A DETAIL BY THE ENGINEER ON THE CURB TIE
 DOWN TO THE ROOF.
 PER SECTION 301.12 WIND RESISTANCE 2007 FBC (M)
 8) REFER TO SECTION 301.12 WIND RESISTANCE REFERRING TO
 WOOD SLEEPERS
 FOR CONDENSATE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  
  
  