Plan Review Notes
Plan Review Notes For Permit 12030295
Permit Number 12030295
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-04-02 13:24:34300 NORTHPOINT PARKWAY - SUITE #305
 PERMIT #12030295
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES SUITE #305 AND THE
 DRAWINGS INDICATE SUITE #300. PLEASE COORDINATE.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 FIRE-RATED WALLS/PARTITIONS SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET A100 - DOOR #18 IS REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHEN SERVING AN OCCUPANT
 LOAD OF MORE THAN 50 PERSONS (1350 SQ.FT. / 15 SQ.FT. =
 90 PERSONS).
  
 SHEET A100 - EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING
 FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM
 POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM
 THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET M2.1 - PROVIDE FIRE DAMPERS FOR DUCTWORK
 PENETRATING FIRE RATED WALL OF TRAINING ROOM.
  
 SHEET FA2.1- PROVIDE FIRE ALARM NOTIFICATION APPLIANCE
 IN BEREAVEMENT LOBBY.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 SHEET FS2.1 - ESTABLISHES BRADLY BROWN AS THE ENGINEER
 OF RECORD FOR THE FIRE SPRINKLER SYSTEM; THEREFORE,
 FIRE SPRINKLER SHOP DRAWINGS PRODUCED BY THE CONTRACTOR
 SHOULD NOT BE SIGNED/SEALED PER FS 633.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  