| 2012-04-02 13:24:34 | 300 NORTHPOINT PARKWAY - SUITE #305 |
| | PERMIT #12030295 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PERMIT APPLICATION INDICATES SUITE #305 AND THE |
| | DRAWINGS INDICATE SUITE #300. PLEASE COORDINATE. |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | FIRE-RATED WALLS/PARTITIONS SHALL BE PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | SHEET A100 - DOOR #18 IS REQUIRED TO SWING IN THE |
| | DIRECTION OF EGRESS TRAVEL WHEN SERVING AN OCCUPANT |
| | LOAD OF MORE THAN 50 PERSONS (1350 SQ.FT. / 15 SQ.FT. = |
| | 90 PERSONS). |
| | |
| | SHEET A100 - EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING |
| | FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM |
| | POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM |
| | THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE |
| | NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET M2.1 - PROVIDE FIRE DAMPERS FOR DUCTWORK |
| | PENETRATING FIRE RATED WALL OF TRAINING ROOM. |
| | |
| | SHEET FA2.1- PROVIDE FIRE ALARM NOTIFICATION APPLIANCE |
| | IN BEREAVEMENT LOBBY. |
| | |
| | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL |
| | INITIATE A GENERAL FIRE ALARM CONDITION. |
| | |
| | SHEET FS2.1 - ESTABLISHES BRADLY BROWN AS THE ENGINEER |
| | OF RECORD FOR THE FIRE SPRINKLER SYSTEM; THEREFORE, |
| | FIRE SPRINKLER SHOP DRAWINGS PRODUCED BY THE CONTRACTOR |
| | SHOULD NOT BE SIGNED/SEALED PER FS 633. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |