| 2012-04-06 10:03:52 | BUILDING PLAN REVIEW |
| | PERMIT: 12030295 |
| | ADD: 300 NORTHPOINT PKWY # 305 |
| | CONT: TRILLIUM CONSTRUCTION, INC |
| | TEL: (561)283-5121 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A100 & A120 INDICATE ROOM # 119 AS A TRAINING |
| | ROOM THAT HAS AN OCCUPANT LOAD OF 87 ( 1292/15= 87), |
| | PLEASE REVIEW 2007/09 FBC-B 1008.1.2 DOORS SHALL SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN |
| | OCCUPANT LOAD OF 50 OR MORE PERSONS. |
| | |
| | 2) SHEET A100 & A120 ROOM # 119 IS INDICATED WITH A 1 |
| | HR FIRE PARTITION NEITHER OF DOORS 18 OR 19 INDICATE |
| | ANY FIRE RATING ON THE DOOR SCHEDULE A100. 2007/09 |
| | FBC-B TABLE 715.4 |
| | |
| | 3) SHEET A100 & A120 THE DOOR LEADING FROM OFFICE TO |
| | WAREHOUSE (DOOR # 8) IN A 1 HOUR RATED FIRE WALL DOES |
| | NOT INDICATE ANY RATING, PLEASE REVIEW 2007/09 FBC-B |
| | TABLE 715.4. |
| | |
| | 4) SHEET A100 & A120 STORAGE ROOM #118 HAS TWO WALLS 1 |
| | HR ATED BECAUSE OF THE ADJOINING OCCUPANCY |
| | CLASSIFICATIONS THE OTHER 2 WALLS ARE DESIGNATED AS A |
| | TYPE (2) WALL. DETAIL # 2 SHEET A600 INDICATES THIS |
| | WALL STOPS 6 INCHES ABOVE THE CEILING. PLEASE REVIEW |
| | 2007/09 FBC-B TABLE 508.2 INCIDENTAL USE AREAS (STORAGE |
| | > 100 SQ FT). PLEASE SEE 508.2.2.1 CONSTRUCTION. WHERE |
| | TABLE 508.2 PERMITS AN AUTOMATIC FIRE-EXTINGUISHING |
| | SYSTEM WITHOUT A FIRE BARRIER, THE INCIDENTAL USE AREA |
| | SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING |
| | BY CONSTRUCTION CAPABLE OF RESISTING THE PASSAGE OF |
| | SMOKE. THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO |
| | THE UNDERSIDE OF THE FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING ASSEMBLY OR FIRE-RESISTANCE-RATED |
| | ROOF/CEILING ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE |
| | FLOOR OR ROOF SHEATHING, OR SUB DECK ABOVE. |
| | SMOKE PARTITIONS 710. |
| | 710.4 CONTINUITY. SMOKE PARTITIONS SHALL EXTEND FROM |
| | THE TOP OF THE FOUNDATION OR FLOOR BELOW TO THE |
| | UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, DECK OR SLAB |
| | ABOVE OR TO THE UNDERSIDE OF THE CEILING ABOVE WHERE |
| | THE CEILING MEMBRANE IS CONSTRUCTED TO LIMIT THE |
| | TRANSFER OF SMOKE. |
| | |
| | 5) 2007/09 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| | AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| | |