Plan Review Notes
Plan Review Notes For Permit 12030295
Permit Number 12030295
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-06 10:03:52BUILDING PLAN REVIEW
 PERMIT: 12030295
 ADD: 300 NORTHPOINT PKWY # 305
 CONT: TRILLIUM CONSTRUCTION, INC
 TEL: (561)283-5121
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A100 & A120 INDICATE ROOM # 119 AS A TRAINING
 ROOM THAT HAS AN OCCUPANT LOAD OF 87 ( 1292/15= 87),
 PLEASE REVIEW 2007/09 FBC-B 1008.1.2 DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 2) SHEET A100 & A120 ROOM # 119 IS INDICATED WITH A 1
 HR FIRE PARTITION NEITHER OF DOORS 18 OR 19 INDICATE
 ANY FIRE RATING ON THE DOOR SCHEDULE A100. 2007/09
 FBC-B TABLE 715.4
  
 3) SHEET A100 & A120 THE DOOR LEADING FROM OFFICE TO
 WAREHOUSE (DOOR # 8) IN A 1 HOUR RATED FIRE WALL DOES
 NOT INDICATE ANY RATING, PLEASE REVIEW 2007/09 FBC-B
 TABLE 715.4.
  
 4) SHEET A100 & A120 STORAGE ROOM #118 HAS TWO WALLS 1
 HR ATED BECAUSE OF THE ADJOINING OCCUPANCY
 CLASSIFICATIONS THE OTHER 2 WALLS ARE DESIGNATED AS A
 TYPE (2) WALL. DETAIL # 2 SHEET A600 INDICATES THIS
 WALL STOPS 6 INCHES ABOVE THE CEILING. PLEASE REVIEW
 2007/09 FBC-B TABLE 508.2 INCIDENTAL USE AREAS (STORAGE
 > 100 SQ FT). PLEASE SEE 508.2.2.1 CONSTRUCTION. WHERE
 TABLE 508.2 PERMITS AN AUTOMATIC FIRE-EXTINGUISHING
 SYSTEM WITHOUT A FIRE BARRIER, THE INCIDENTAL USE AREA
 SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING
 BY CONSTRUCTION CAPABLE OF RESISTING THE PASSAGE OF
 SMOKE. THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO
 THE UNDERSIDE OF THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING ASSEMBLY OR FIRE-RESISTANCE-RATED
 ROOF/CEILING ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, OR SUB DECK ABOVE.
 SMOKE PARTITIONS 710.
 710.4 CONTINUITY. SMOKE PARTITIONS SHALL EXTEND FROM
 THE TOP OF THE FOUNDATION OR FLOOR BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, DECK OR SLAB
 ABOVE OR TO THE UNDERSIDE OF THE CEILING ABOVE WHERE
 THE CEILING MEMBRANE IS CONSTRUCTED TO LIMIT THE
 TRANSFER OF SMOKE.
  
 5) 2007/09 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP


Account Summary | Usage Policy | Privacy Policy