| Plan Review Notes For Permit 12030294 |
| Permit Number |
12030294 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-12-12 10:51:11 | 12030294 | | | 2401 SPRUCE AVENUE | | | COMMERCIAL RENOVATION | | | | | | THE FOLLOWING ITEMS HAVE BEEN NOTED AS A PROVISO ON THE | | | PLANS. | | | | | | VERIFY THE LIGHTING DENSITY IS COMPLIANT WITH THE 2007 | | | FLORIDA BUILDING ENERGY CODE REQUIREMENTS. | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | | DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO | | | THE DESIGN. 2005 NEC 110.22, 110.16 | | | | | | PROVIDE A SUMMARY LOAD CALCULATION. 2005 NEC 215.2 | | | | | | PROVIDE A FEEDER AND CONDUIT SCHEDULE FOR PANEL "AD". | | | 2005 NEC 215.5 | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA AND | | | FIRE ALARM SYSTEMS. | | | | | | PLEASE CALL IF FURTHER CLARIFICATION IS NEEDED. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|