2012-12-12 10:51:1112030294
 2401 SPRUCE AVENUE
 COMMERCIAL RENOVATION
  
 THE FOLLOWING ITEMS HAVE BEEN NOTED AS A PROVISO ON THE
 PLANS.
  
 VERIFY THE LIGHTING DENSITY IS COMPLIANT WITH THE 2007
 FLORIDA BUILDING ENERGY CODE REQUIREMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO
 THE DESIGN. 2005 NEC 110.22, 110.16
  
 PROVIDE A SUMMARY LOAD CALCULATION. 2005 NEC 215.2
  
 PROVIDE A FEEDER AND CONDUIT SCHEDULE FOR PANEL "AD".
 2005 NEC 215.5
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA AND
 FIRE ALARM SYSTEMS.
  
 PLEASE CALL IF FURTHER CLARIFICATION IS NEEDED.
  