| Plan Review Notes For Permit 12030294 |
| Permit Number |
12030294 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-12-11 13:38:17 | *** DENIED *** | | | 1) PLAN M-1 SHOWS 5 LOCATIONS WERE DUCTS ARE | | | PENETRATING 1 HR. FIRE RATED | | | WALLS WITH NO FIRE DAMPERS, PLEASE REVISE MECH. PLAN TO | | | COMPLY WITH 2007 FBC/M (B) 607.5.3. | | | 2) OUTDOOR AIR CALCULATIONS ON PLAN M-1 APPEAR TO BE | | | INCORRECT, SEE 2007 | | | FBC/M 403.3 AND TABLE 403.3 OR SEE 403.3.2. PLEASE | | | SUBMIT REVISED | | | OUTDOOR AIR CAL'S. WITH CALCULATIONS FOR REVIEW BEFORE | | | INSPECTION. | | | **MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD INC.) | | | **FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|