Plan Review Notes
Plan Review Notes For Permit 12030294
Permit Number 12030294
Review Stop M
Sequence Number 2
Notes
Date Text
2012-12-11 13:38:17*** DENIED ***
 1) PLAN M-1 SHOWS 5 LOCATIONS WERE DUCTS ARE
 PENETRATING 1 HR. FIRE RATED
 WALLS WITH NO FIRE DAMPERS, PLEASE REVISE MECH. PLAN TO
 COMPLY WITH 2007 FBC/M (B) 607.5.3.
 2) OUTDOOR AIR CALCULATIONS ON PLAN M-1 APPEAR TO BE
 INCORRECT, SEE 2007
 FBC/M 403.3 AND TABLE 403.3 OR SEE 403.3.2. PLEASE
 SUBMIT REVISED
 OUTDOOR AIR CAL'S. WITH CALCULATIONS FOR REVIEW BEFORE
 INSPECTION.