| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | CONFIRM ALL EXISTING EXTERIOR EXIT DOORS ARE EQUIPPED |
| | WITH PANIC HARDWARE. |
| | |
| | PART OF THE ASSEMBLY OCCUPANCY APPEARS TO EXIT THROUGH |
| | THE BUSINESS OCCUPANCY. WHERE EXIT ACCESS FROM AN |
| | OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE |
| | OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY PER |
| | NFPA 101 SECTION 6.1.14.1.2. |
| | |
| | NO INFORMATION PROVIDED FOR PHASE III. WILL THIS BE |
| | EMPTY SHELL SPACE OR STORAGE DURING PHASE I AND II? |
| | WHAT IS THE OCCUPANT LOAD FOR PHASE III? |
| | |
| | ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION |
| | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| | FOR A SUB-PERMIT. FOR ISSUANCE OF A GENERAL BUILDING |
| | PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| | CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| | DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| | AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE |
| | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | FIRE ALARM: PROVIDE VISUAL NOTIFICATION APPLIANCE IN |
| | ALL PUBLIC AND COMMON USE SPACES. |
| | |
| | FIRE ALARM: PROVIDE SPEAKER/STROBE NOTIFICATION |
| | APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT |
| | LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM |
| | NOTIFICATION BY VISIBLE SIGNALS AND VOICE |
| | ANNOUNCEMENTS. REFERENCE SECTION 12.3.4.3.3 OF FLORIDA |
| | FIRE PREVENTION CODE ? NFPA 101 |
| | |
| | FIRE ALARM: PROVIDE A PRE-RECORDED FIRE ALARM |
| | EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS |
| | BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, |
| | AND EXIT THE BUILDING IMMEDIATELY. |
| | |