| Plan Review Notes For Permit 12030294 |
| Permit Number |
12030294 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-11-26 12:57:32 | THE FOLLOWING ELECTRICAL REVIEW COMMENTS FROM 10/1/12 | | | WERE NOT ADDRESSED IN THE REVISION SUBMITTED. | | | | | | 12030294 | | | 2401 SPRUCE AVENUE | | | COMMERCIAL RENOVATION | | | | | | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW | | | COMMENTS. | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY VERIFYING COMPLIANCE | | | WITH THE 2010 FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC EC 505.5.3 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | | DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO | | | THE DESIGN. 2005 NEC 110.22, 110.16 | | | | | | PROVIDE A SUMMARY LOAD CALCULATION. 2005 NEC 215.2 | | | | | | PROVIDE A FEEDER AND CONDUIT SCHEDULE FOR PANEL "AD". | | | 2005 NEC 215.5 | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA AND | | | FIRE ALARM SYSTEMS. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|