Plan Review Notes
Plan Review Notes For Permit 12030294
Permit Number 12030294
Review Stop E
Sequence Number 2
Notes
Date Text
2012-11-26 12:57:32THE FOLLOWING ELECTRICAL REVIEW COMMENTS FROM 10/1/12
 WERE NOT ADDRESSED IN THE REVISION SUBMITTED.
  
 12030294
 2401 SPRUCE AVENUE
 COMMERCIAL RENOVATION
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY VERIFYING COMPLIANCE
 WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC EC 505.5.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO
 THE DESIGN. 2005 NEC 110.22, 110.16
  
 PROVIDE A SUMMARY LOAD CALCULATION. 2005 NEC 215.2
  
 PROVIDE A FEEDER AND CONDUIT SCHEDULE FOR PANEL "AD".
 2005 NEC 215.5
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA AND
 FIRE ALARM SYSTEMS.
  