| Plan Review Notes For Permit 12030294 |
| Permit Number |
12030294 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-03 13:45:28 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. SHEET A-1.1: PER P-403.7 A UNISEX RESTROOM IS | | | REQUIRED. | | | | | | 2. SHEET A-10 PLEASE SHOW THE GRAB BARS IN THE REQUIRED | | | AMBULITORY STALLS: | | | FBC 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE | | | PROVIDED, THEN AT LEAST ONE SHALL BE A STANDARD TOILET | | | STALL COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE | | | STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING | | | WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES | | | (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING | | | DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D) | | | AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN | | | SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. | | | | | | 3. NO PLUMBING DRAWINGS WERE FOUND WITH THIS SET OF | | | PLANS. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|