2012-10-22 14:40:53PLANS DENIED
 1) SHOW RATED WALLS ON MECHANICAL PLANS
 PER SECTION 107 FBC AND 607.5.1 FIRE WALLS
 2) PROVIDE DETAILS ON CONDENSER STAND TO ROOF TIE DOWN
 AND CONDENSER TO STAND TIE DOWN.PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M)
 3) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 FBC
 (M)
 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE