| Plan Review Notes For Permit 12030294 |
| Permit Number |
12030294 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-22 14:40:53 | PLANS DENIED | | | 1) SHOW RATED WALLS ON MECHANICAL PLANS | | | PER SECTION 107 FBC AND 607.5.1 FIRE WALLS | | | 2) PROVIDE DETAILS ON CONDENSER STAND TO ROOF TIE DOWN | | | AND CONDENSER TO STAND TIE DOWN.PER SECTION 301.12 | | | WIND RESISTANCE 2010 FBC (M) | | | 3) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 FBC | | | (M) | | | 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS | | | 2010 FLORIDA ENERGY CODE | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | |
|