| Plan Review Notes For Permit 12030280 |
| Permit Number |
12030280 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-26 11:08:33 | PLANS DENIED | | | 1) SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR | | | FIRE SUPPRESSION TO HOOD. | | | 2) CAN NOT READ DETAILS FOR CURB'S TO ROOF TIE DOWN PER | | | SECTION 106.1.3 FBC 2007 | | | 3) REFER TO SECTION 506.3.12.1 TERMINATION ABOVE THE | | | ROOF. 2007 FBC (M) | | | 4) REFER TOSECTION506.3.6 GREASE DUCT CLEARANCE 2007 | | | FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|