2012-04-10 17:55:0012030240
 6701 N. JOG ROAD
 SWA WAREHOUSE
  
 E3-001
 VERIFY THE 112 ? KVA TRANSFORMERS OR LARGER ARE LOCATED
 WITHIN FIRE-RESISTANT ROOMS WITH A ONE HOUR FIRE RATING
 OR COMPLY WITH THE NEC EXCEPTIONS. NEC 450.21 (B)
 PROVIDE A GROUNDED CONDUCTOR WHICH MAY BE BROUGHT TO
 THE SERVICE EQUIPMENT AT THE MAINTENANCE BUILDING AND
 THE VISITOR?S CENTER. NEC 250.24 (C)
 IF A HIGH IMPEDANCE GROUNDING SYSTEM IS TO BE UTILIZED
 A DETAIL IS REQUIRED. NEC 250.36
 A GFCI GENERAL PURPOSE RECEPTACLE IS REQUIRED AT AN
 ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR
 CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC 210.63
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
 CLARIFY HOW THE TRANSFER FROM NORMAL POWER TO EMERGENCY
 POWER WILL BE MANAGED. CLARIFY HOW THE GROUNDING AND
 BONDING BETWEEN THE TWO SYSTEMS WILL BE HANDLED
 INCLUDING THE MAIN BONDING JUMPER TO THE GROUNDED
 CONDUCTOR. NEC 215.5. 250
 E7-002
 PROVIDE DETAIL FOR BONDING METAL PULL BOX COVERS. NEC
 314.30(D)
 PROVIDE PULL BOX DIMENSIONS. NEC 314
 E4-101
 ALL RECEPTACLES LOCATED OUTDOORS IN BATHROOMS OR WITH
 IN SIX FEET OF A SINK MUST BE GFCI PROTECTED. NEC 210.8
 PROVIDE A DETAIL WHICH ILLUSTRATES THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED AS REQUIRED FOR THE ELECTRICAL EQUIPMENT AND
 PANEL BOARDS. NEC 110.26, 240.24, 408.17
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING
 THE SIZE AND TYPE OF HAZARDS. NEC 110.22, 110.16
 E4-103
 PROVIDE DIMENSIONS FOR THE DUCT BANK. NEC 310.16
 PROVIDE ELECTRICAL DETAIL FOR FUELING STATION WIRING
 METHODS. NEC 215.5
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE
 AND DATA.
 A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING
 FOR POLES, BASES AND FIXTURES IS REQUIRED.
  