| 2012-04-02 15:05:59 | BUILDING PLAN REVIEW |
| | PERMIT: 12030240 |
| | ADD: 6701 N JOG RD |
| | CONT: LEBOLO CONSTRUCTION |
| | TEL: (561)541-0191 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE BUILDING CODE SUMMARY SHEET 720-A5-100 INDICATES |
| | THIS BUILDING IS TO BE FIRE SPRINKLERED, THE INDEX |
| | SHEET 720-G0-002 DOES NOT INDICATE ANY FIRE SPRINKLER |
| | PLANS FOR THE BUILDING ITSELF. 2007/09 FBC-B MINIMUM |
| | PLAN REVIEW CRITERIA FOR BUILDINGS 106.3.5.1.1(5) FIRE |
| | SUPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE |
| | SPRINKLERS . |
| | |
| | 2) 109.3.7(1) SPECIAL INSPECTOR IS REQUIRED FOR ALL |
| | TYPE I OR TPYE II BUILDINGS . FBC* 109.3.7 RESIDENT |
| | INSPECTOR. SUBMIT INSPECTOR RESUME' AND LICENSE |
| | DOCUMENTS TO KEN CONRAD , DIRECTOR OF THE RESIDENT |
| | (SPECIAL) INSPECTOR PROGRAM. A RESIDENT INSPECTOR |
| | PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO ONE OR |
| | MORE OF THE FOLLOWING: - BUILDINGS/ADDITIONS OF TYPE I |
| | OR II CONSTRUCTION. CONTACT KEN CONRAD AT (561) |
| | 805-6666. |
| | |
| | 3) THE PLANS DO PROVIDE THE MINIMUM SAFE BEARING VALUE |
| | FOR THE SOIL TO BE 4,000 PSF (SHEET 720-S3-101), NO |
| | SOILS REPORT INDICATING HOW TO OBTAIN THE MINIMUM SAFE |
| | BEARING FOR THIS BUILDING. 2007/09 FBC-B 1802.6 |
| | REPORTS. |
| | |
| | 4) A SEPERATE PERMIT APPLICATION REVIEW AND ASSOCIATED |
| | FEES SHOULD BE MADE FOR THE FUEL STATION FOUND ON SHEET |
| | 720-S4-101. PLEASE PROVIDE ADDITIONAL INFORMATION AS TO |
| | WHAT TYPE OF TANK WILL BE INSTALLED. PLEASE REVIEW |
| | 2007/09 FBC-B 414.6. OUTDOOR STORAGE, DISPENSING AND |
| | USE. THE OUTDOOR STORAGE , DISPENSING AND USE OF |
| | HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 5) SHEET 720-S6-000. THIS STRUCTURAL SHEET INDICATES |
| | THE BUILDING DESIGN TO THE: |
| | 2007/09 FBC-B ASCE 7-05 |
| | 140 MPH WIND ZONE |
| | 1.15 IMPORTANCE FACTOR |
| | PLEASE PROVIDE WHY THE LOWER ROOF HAS A FACTORY-MUTUAL |
| | FM-105 WIND RATING M-1 TO M-3 & M-5 TO M-9 AAND THE |
| | UPPER ROOF A FACTORY-MUTUAL FM-120 WIND RATING FROM M-3 |
| | TO M-5? |
| | IT WOULD APPEAR THIS TO BE ANOTHER WIND DESIGN FROM |
| | ASCE 7-05? ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS, TRANSLUCENT WALL PANELS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 8) THE CODE SUMMARY / LIFESAFETY SHEET INDICATES PART |
| | OF THE BUILDING AS A S-2 OCCUPANCY, PLEASE PREOVIDE |
| | WHAT TYPES OF ITEMS WILL BE STORED IN THE WAREHOUSE |
| | PORTION AND WHAT WOULD BE STORED INTHE INSULATED |
| | STORAGE AREA? AND AT WHAT AMOUNTS? |
| | |
| | 9) THE LIFE SAFETY SHEET DOES NOT INDICATE ANY EGRESS |
| | PATHS IN THE WAREHOUSE AREA NOR ANY EMERGENCY LIGHTING, |
| | 2007/09 FBC TABLE 1006 INDICATES AAN EXCEPTION THAT IS |
| | WHEN THIS IS ONLY DAYLIGHT OPERATIONS, WILL THIS |
| | FACILITY BE OCCUPIED AT NIGHT? |
| | |
| | 10) PRE-ENGINEERED EQUIPMENT MEZZANINE, FOUND ON SHEET |
| | 720-A3-104 WILL NEED TO PROVIDE MANUFACTURERS |
| | SPECIFICATION ON THE FRAMING SYSTEM, FLOORING SYSTEM, |
| | STAIR/ LADDER AND GUARDRAIL SYSTEM AS WELL AS THE SAFE |
| | ALLOWABLE FLOOR LOADING OF THE MEZZANINE. FBC-B |
| | 110.4.2. |
| | |
| | 11) SHEET 720-A1-101 INDICATES EXTERIOR BOTTLE STORAGE, |
| | PLEASE PROVIDE THE TYPES OF GASSSES, THE SIZE OF THE |
| | CONTAINERS, IN CUBIC FT. 2007/09 FBC-B 2007/09 FBC-B |
| | 414.6. OUTDOOR STORAGE, DISPENSING AND USE. THE OUTDOOR |
| | STORAGE , DISPENSING AND USE OF HAZARDOUS MATERIALS |
| | SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | JAMES A. WITMER CBO |