| Plan Review Notes For Permit 12030207 |
| Permit Number |
12030207 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-09 15:13:53 | 215 CLEMATIS STREET | | | PERMIT #12030207 | | | MASTER #11100370 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE STROBE DEVICE IN SMALL BATHROOM. | | | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|