| 2013-04-17 15:44:35 | 7670 OKEECHOBEE BOULEVARD |
| | PERMIT #12030147 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET A1.1: PANIC/FIRE EXIT HARDWARE IS NEEDED IN |
| | ASSEMBLY OCCUPANCIES WHERE THE DOOR SERVES 50 OR |
| | PERSONS. DOOR #100, 101, 102, 107 & 108 WILL REQUIRE |
| | PANIC/FIRE EXIT HARDWARE. CURRENTLY THE SPECIFICATIONS |
| | DO NOT INDICATE THIS TYPE OF HARDWARE FOR THESE DOORS. |
| | |
| | SHEET A1.2: PANIC/FIRE EXIT HARDWARE IS NEEDED IN |
| | ASSEMBLY OCCUPANCIES WHERE THE DOOR SERVES 50 OR |
| | PERSONS. DOOR #201, 214, 218, 220, 223 & 224 WILL |
| | REQUIRE PANIC/FIRE EXIT HARDWARE. CURRENTLY THE |
| | SPECIFICATIONS DO NOT INDICATE THIS TYPE OF HARDWARE |
| | FOR THESE DOORS. |
| | |
| | SHEET E2-3: AN EXIT SIGN IS NEEDED AT THE SECONDARY |
| | EGRESS DOOR IN BREAKROOM #307. |
| | |
| | ELECTRICAL DRAWINGS: THE FIRE ALARM SYSTEM WILL NEED TO |
| | BE EQUIPPED WITH VOICE EVACUATION CAPABILITIES FOR AN |
| | ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN |
| | 300 PERSONS. PROVIDE SPEAKER/STROBE NOTIFICATION |
| | APPLIANCES (REFERENCE SECTION 12.3.4.3.3 OF FLORIDA |
| | FIRE PREVENTION CODE - NFPA 101). PROVIDE A |
| | PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING |
| | OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE |
| | BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| | BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE |
| | |
| | INSPECTOR NOTES: THE BUILDING IS FUNCTIONING AS A MIXED |
| | OCCUPANCY (NON-SEPARATED ASSEMBLY AND BUSINESS) THAT |
| | WILL NEED A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND |
| | PANIC/FIRE EXIT HARDWARE ON EGRESS DOORS. |