| Plan Review Notes For Permit 12030147 |
| Permit Number |
12030147 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-12-04 17:32:05 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2010 | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. NOT COMPLIED. THE 8X8 EXHAUST DUCT PENETRATING THE | | | SHAFT ENCLOSURE ON PAGE M2-2 IS MISSING A FIRE/SMOKE | | | DAMPER. SEE DRAWING MARK-UP IN PROJECTDOX FOR EXACT | | | LOCATION. | | | | | | 2. OK | | | | | | 3. OK | | | | | | 4. OK | | | | | | 5. NOT COMPLIED. THE UPER DETAIL FOR THE STAND CALLS | | | FOR GALVANIZED STEEL PIPE SUPPORTS, WHILE THE LOWER | | | DETAIL CALLS FOR A PRE-MANUFACTURED STAND. WHICH IS | | | CORRECT? IF A PRE-MANUFACTURED STAND IS TO BE USED, | | | PROVIDE THE ACTUAL PRODUCT APPROVAL FOR THE STAND, | | | APPROVED IN WRITING BY THE ENGINEER FOR THIS PROJECT | | | PER FBC-B 106.3.3. | | | | | | 6. NOT COMPLIED. SHOW ALL DUCT MOUNTED SMOKE DETECTORS | | | ON THE MECHANICAL SHEETS. CODE COMPLIANCE OF THE | | | DETECTOR LOCATION CANNOT BE DETERMINED BY SHOWING | | | DETECTORS ON AN ELECTRICAL SHEET WHICH DOES NOT SHOW | | | THE HVAC DISTRIBUTION SYSTEM. FBC-M 606.2.1 AND FBC-B | | | 106.1. | | | | | | 7. NOT COMPLIED. SEE COMMENT #6 ABOVE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|