| 2012-10-01 15:41:29 | BUILDING PLAN REVIEW |
| | PERMIT: 12030147 |
| | ADD: 7670 OKEECHOBEE BLVD |
| | CONT:TBD |
| | TEL: (561)###-#### |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | NEW 3 STORY TYPE II-B SPRINKLERED BUILDING |
| | |
| | 2ND REVIEW |
| | OCT. 01/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) 2ND REQUEST, LS1-1 & A1-1, THE PLANS INDICATE RATED |
| | TENANT SEPARATION WALLS THAT DOUBLE AS CORRIDOR WALLS, |
| | BUT WHERE THE TENANT SEPERATION WALLS CONTINUE AROUND |
| | THE VARIOUS COMMON ELEMENT ROOMS (RESTROOMS, ELECTRICAL |
| | AND OR MECHANICAL ROOMS) THE ONE HOUR RATING IS |
| | MISSING. 2007/09 FBC-B 708.1(7). THE EXCEPTION BETWEEN |
| | BUSINESS OCCUPANCIES UP TO 3,000 SQUARE FEET WITHOUT |
| | RATED TENANT SPERATION WALLS WOULD BE SUITES ON THE |
| | SAME SIDE OF A CORRIDOR WHERE THE TOTAL OF TWO OR MORE |
| | SUITES WOULD BE A TOTAL OF UNDER 3,000 SQUARE FEET. AS |
| | DEPICTED ON THE LS SHEET THE AREAS OF CONCERN ARE |
| | INDICATED WITHIN THE TENANT SPACE. |
| | |
| | 3) 2ND REQUEST, LS1-1 & A1-1, THE PLANS ROOM TYPES, |
| | SOME OF THESE ROOM HAVE INCIDENTAL USE AREAS (TABLE |
| | 508.2 INCIDENTAL USE AREAS) ( MECHANICAL AND OR STORAGE |
| | ROOM < 100 S F) ) AND NEED TO CONSTRUCT THE WALLS IN |
| | ACCORDANCE WITH 2007/09 FBC-B 508.2.2.1 (SMOKE |
| | PARTITIONS). |
| | |
| | 4) COMPLIED. |
| | |
| | 5A) 2ND REQUEST, SHEET LS1-2 & A1-2, PLANS NOW INDICATE |
| | THE ROOM USAGE AND THE CONFERENCE ROOM AREA OF 1440 SQ |
| | FT CREATES AN A-3 OCCUPANCY, THE COVER SHEET INDICATED |
| | A LOADING OF 15 SQUARE FEET PER PERSON, OR A OCCUPANT |
| | LOAD OF 96. THE 1440 SQUARE FEET CREATES AN ACCESSORY |
| | OCCUPANCY |
| | 2007FBC-B 508.3.1 THAT WILL REQUIRE FIRE RATED |
| | CORRIDORS PER 2007 FBC-B TABLE 1017.1. |
| | |
| | 5B) THE SAME HOLDS TRUE FOR THE MULTIPURPOSE ROOM # |
| | 206, THIS ROOM IS APPROXIMATELY 2340 SQUARE FEET, BEING |
| | A MULTIPURPOSE ROOM AGAIN WE WILL BE TAKING THE WORST |
| | CASE SENARIO WITH 7 SQ FT PER PERSON, THIS ROOM WOULD |
| | ALSO BE CONSIDERED AN A-3 OCCUPANCY. |
| | |
| | 5C) IN BOTH ROOMS PLEASE PROVIDE A FURNATURE PLAN THAT |
| | WILL REDUCE THE OCCUPANT LOADS AND BRING THE REQUIRED |
| | DOOR WIDTH AND STAIR WIDTH BACK INTO COMPLIANCE. 2007 |
| | FBC-B 1005.1. PLEASE NOTE WITH THE OCCUPANT LOAD TAKEN |
| | AT 7 SQUARE FEET FOR THE CONFERENCE ROOM AND |
| | MULTI-PURPOSE ROOM WOULD CREATE AN OCCUPANT LOAD OF |
| | OVER 500 REQUIRING A THIRD EXIT, 2007 FBC-B TABLE |
| | 1019.1. |
| | |
| | COMMENT FROM 1ST REVIEW.THE PLANS DO NOT INDICATE ROOM |
| | TYPES, SOME OF THESE ROOM MAY BE INCIDENTAL USE AREAS |
| | AND NEED TO CONSTRUCT THE WALLS IN ACCORDANCE WITH |
| | 2007/09 FBC-B 508.2.2.1 (SMOKE PARTITIONS). |
| | |
| | 6A) 2ND REQUEST. SHEET A1-1 THE ELEVATOR MACHINE ROOM |
| | DOES NOT INDICATE RATED WALLS 3006.4. PLEASE SHOW ALL |
| | FIRE AND OR SMOKE RATED WALLS ON A1-1, A1-2 AND A1-3 |
| | SINCE THE ROOMS AND DOORS ARE IDENTIFIED. 106.1.2. |
| | ADDITIONAL DATA. INDICATE ALL FIRE RATED WALLS, SMOKE |
| | PARTITIONS ON THE A1 SHEETS FOR ALL THREE STORIES, |
| | THERE ARE MANY WALLS THAT DO NOT INDICATE FIRE RATED |
| | WALLS |
| | |
| | .6B) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) 2ND REQUEST, SHEET A2-1 THE PRE-ENGINEERED ROOF |
| | ACCESS HATCH REQUIRES EITHER A FL STATE APPROVAL OR |
| | MIAMI-DADE NOA, RULE 9N-3(31)(A). |
| | |
| | 9) 2ND REQUEST, SHEET A2-1 THE PRE-ENGINEERED A/C |
| | STANDS WILL ALSO REQUIRE EITHER A FL APPROVAL OR |
| | MIAMI-DADE NOA. RULE 9N-3(31)(G). |
| | |
| | 10) SHEET A2-1 INDICATES THREE ROOMS 2 WITH |
| | APRROXIMATELY 6'-0" IN HEIGHT THE THIRD APPROXIMATELY |
| | 8'-0 IN HEIGHT, WHAT WILL THESE ROOMS BE USED FOR? |
| | FBC-B 1509.2. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) 2ND REQUEST, RESPONCE NOTED. SHEET A4-1, A 4-2 & |
| | A4-3 DETAIL # 10 PLEASE PROVIDE PRODUCT |
| | SPECIFICATIONS.2007/09 FBC-B 1406.2.2 ARCHITECTURAL |
| | TRIM. ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192 |
| | MM) IN HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF |
| | APPROVED NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED |
| | TO THE WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE |
| | BRACKETS. |
| | |
| | 13) SEMI- COMPLIED. SHEET A4-1 & A4-3 DETAIL # 17 |
| | GAURDRAILS SEE OPENING LIMITATION OF 4 INCHES 1013.3 |
| | FBC-B. |
| | |
| | 14) COMPLIED AS NOTED: ASSISSTANTS DESK. |
| | |
| | 15) 2ND REQUEST, ONCE ALL THE FIRE & SMOKE RATED WALLS |
| | ARE IDENTIFIED THE DOOR SCHEDULE WILL NEED TO BE |
| | UPDATED. 2007/09 FBC-B TABLE 715.4. |
| | |
| | 16) COMPLIED. |
| | |
| | 17) S1-2 THIS STRUCTURE WILL REQUIRE A SPECIAL |
| | INSPECTOR WPB ADMINISTRATIVE CODE 109.3.7 BUILDINGS |
| | MORE THAN 2 STORIES IN HEIGHT, AND TILT WALL |
| | CONSTRUCTION. CONTACT KEN CONRAD FOR REQUIRED LICENSING |
| | AND FORMS AT 561-805-6666. |
| | |
| | 18) COMPLIED. |
| | |
| | |
| | |
| | 19) 2ND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 20) 2ND REQUEST, COMPONENTS & CLADDING FBC-B 1609. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 21) COMPLIED AS NOTED, EXTERIOR GLAZING WILL BE LARGE |
| | MISSILE IMACT. |
| | |
| | 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |