| 2012-04-17 16:09:01 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGES M2-2 AND M2-3: DUCT PENETRATIONS OF THE SHAFT |
| | ENCLOSURES ADJACENT TO THE ELEVATOR SHALL BE PROTECTED |
| | BY FIRE AND SMOKE DAMPERS PER FBC-M 607.5.5. |
| | |
| | 2. PAGE M2-3: THERE IS A FOOTNOTE #3 POINTING AT THE |
| | FRESH AIR DUCT FROM THE ROOF. HOWEVER, THERE IS NO TEXT |
| | ON THIS PAGE ASSOCIATED WITH THIS FOOTNOTE. PLEASE |
| | CLARIFY. FBC-B 106.1. |
| | |
| | 3. PAGE M2-3: AHU #14 RETURN DROPS ARE SHOWN ON FLOOR |
| | PLAN AS EXHAUST DROPS. PLEASE CLARIFY. BALANCED RETURN |
| | IS REQUIRED PER FBC-M 601.4. |
| | |
| | 4. PAGE M2-2: AHU #5 FRESH AIR MOTORIZED DAMPER IS NOT |
| | SHOWN IN THE CORRECT LOCATION. SHOW THE MOTORIZED |
| | DAMPER IN THE FRESH AIR DUCT PER FBC-B 13-409.AB.3.3. |
| | |
| | 5. PAGE M4-2 AND M4-2A KEY NOTE #4 REFERS TO A DETAIL |
| | FOR THE CONDENSER STANDS ON PAGE M5-1. NO SUCH DETAIL |
| | COULD BE FOUND ON THAT PAGE. PLEASE CLARIFY WHETHER |
| | THESE CONDENSER STANDS ARE SITE BUILT WITH CUSTOM |
| | ENGINEERING OR IF THEY ARE PRE-ENGINEERED, MANUFACTURED |
| | STANDS. IF THE PRE-ENGINEERED STANDS ARE USED, A |
| | PRODUCT APPROVAL FOR THE STANDS IS REQUIRED TO BE |
| | SUBMITTED PER FAC RULE 9N-1. |
| | |
| | 6. PAGE M2-2: DUCT SMOKE DETECTOR REQUIRED IN SUPPLY |
| | SIDE OF AHU #4 PER FBC-M 606.2.1. |
| | |
| | 7. PAGE M2-3: DUCT SMOKE DETECTOR REQUIRED IN SUPPLY |
| | SIDE OF AHU #15 PER FBC-M 606.2.1. |
| | |