| 2012-04-06 13:43:36 | 7670 OKEECHOBEE BOULEVARD |
| | PERMIT #12030147 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: ALL CONSTRUCTION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. SMOKING SHALL BE PROHIBITED |
| | EXCEPT IN DESIGNATED AREAS OUTSIDE THE BUILDING. ALL |
| | INTERIOR CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" |
| | SIGNS POSTED. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | GENERAL: PROVIDE BUILDING ADDRESS VISIBLE FROM THE |
| | STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND |
| | BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND |
| | SHALL CONTRAST THE BACKGROUND. |
| | |
| | GENERAL: PORTABLE FIRE EXTINGUISHERS SHALL HAVE A |
| | MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A |
| | LICENSED FIRE EXTINGUISHER COMPANY. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: WHEN IDENTIFYING THE FIRE RATED WALLS WITH |
| | SIGNAGE OR STENCILING, THE CHARACTERS SHALL BE AT LEAST |
| | 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | |
| | GENERAL: NO INTERIOR FINISH CLASSIFICATIONS INDICATED |
| | FOR WALL AND CEILING MATERIALS. |
| | |
| | SHEET C6: FIRE DEPARTMENT CONNECTION SHALL BE |
| | IDENTIFIED WITH A SIGN STATING, "NO PARKING - FIRE DEPT |
| | CONNECTION". THIS WILL CAUSE THE REMOVAL OF 1 OF 9 |
| | PARKING SPACES. |
| | |
| | SHEET C6: CONFIRM THE FIRE DEPARTMENT CONNECTIONS AND |
| | FIRE HYDRANTS WILL BE PROVIDED WITH CLEARANCES OF 7?-6? |
| | TO THE FRONT AND SIDES AND 4? TO THE BACKSIDE PER |
| | SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. |
| | |
| | SHEET C6: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES |
| | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| | POSITION. |
| | |
| | SHEET C6: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | SHEET C6: PROVIDE PERMANENT WEATHERPROOF SIGN MARKING |
| | THE FIRE DEPARTMENT CONNECTION AND IDENTIFY THE |
| | BUILDING BEING SERVED. |
| | |
| | SHEET LS1-1 AND FP1-0: UPDATE THE CODE LIST TO |
| | REFERENCE THE 2010 EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH |
| | NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. FIRE |
| | SPRINKLER DESIGN SHALL CONFORM TO THE 2007 EDITION OF |
| | NFPA 13. |
| | |
| | **SHEET LS1-1: THE BUILDING IS FUNCTIONING AS A |
| | NON-SEPARATED MULTIUSE OCCUPANCY. THE OCCUPANCY TYPE IS |
| | INDICATED AS BUSINESS; HOWEVER, MULTIPURPOSE ROOM #206 |
| | AND CONFERENCE ROOM #208 ARE FUNCTIONING AS ASSEMBLY |
| | OCCUPANCIES. |
| | |
| | SHEET LS1-1: BOTH STAIR ENCLOSURES DISCHARGE INSIDE THE |
| | BUILDING. PER SECTION 7.7 (NFPA 101), NOT MORE THAN 50% |
| | OF THE EXITS ARE ALLOWED TO DISCHARGE INSIDE THE |
| | BUILDING. |
| | |
| | SHEET A7-1: PROVIDE THE DOOR SCHEDULE HARDWARE GROUP |
| | INFORMATION (LOCKS, LATCHES, CLOSERS, PANIC HARDWARE, |
| | ETC.) |
| | |
| | MECHANICAL: PROVIDE DUCT SMOKE DETECTORS FOR AIR |
| | SYSTEMS EXCEEDING 2000 CFM. |
| | |
| | ELECTRICAL: MONITOR FIRE SPRINKLER TAMPER SWITCHES, |
| | FLOW SWITCHES, AND CLEAN AGENT SUPPRESSION SYSTEM. |
| | PROVIDE/MONITOR TAMPER SWITCHES ON BACKFLOW PREVENTER. |
| | |
| | SHEET E2-2: ONLY TWO EXIT SIGNS PROVIDED FOR ENTIRE |
| | FLOOR. |
| | |
| | SHEET E2-3: ONLY TWO EXIT SIGNS PROVIDED FOR ENTIRE |
| | FLOOR. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |