| Date |
Text |
| 2012-04-17 12:13:01 | 401 SOUTH DIXIE HIGHWAY |
| | PERMIT #12030123 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NEW: RECOMMEND PROVIDING A LIFE SAFETY PLAN SHOWING ALL |
| | EXITS, FIRE RATED WALLS, TENANT SEPARATION WALLS, EXIT |
| | SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON |
| | PATH OF TRAVEL, OCCUPANCY TYPES ETC. |
| | |
| | REPEAT COMMENT: TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED AREAS. ALL OTHER |
| | DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. |
| | |
| | REPEAT COMMENT: WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | REPEAT COMMENT: FIRE PROTECTION SYSTEMS SHALL REMAIN |
| | ACTIVE DURING DEMOLITION AND RENOVATION ACTIVITIES. IN |
| | THE EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE |
| | FOR MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY |
| | THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH |
| | DIXIE HIGHWAY. |
| | |
| | REPEAT COMMENT: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | REPEAT COMMENT: PROVIDE PORTABLE FIRE EXTINGUISHERS. |
| | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| | COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT |
| | EXCEED 75 FEET. |
| | |
| | REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED |
| | EXIT DOORS WITH EXIT SIGNS. |
| | |
| | REPEAT COMMENT: NO ELECTRICAL OR MECHANICAL PLANS |
| | SUBMITTED. |
| | |
| | SHEET A-1.0: |
| | REPEAT COMMENT: THE DEMOLITION PLAN SHOWS THE EXIT |
| | PASSAGEWAY BEING REMOVED FROM THE NORTH STAIR. THIS |
| | REMOVAL WILL RESULT IN OCCUPANTS HAVING TO LEAVE THE |
| | FIRE RATED STAIR ENCLOSURE AND EGRESS THROUGH THE |
| | LOBBY. |
| | |
| | NEW: THE RESPONSE LETTER DATED MARCH 29, 2012 INDICATES |
| | THE SOUTH STAIR EXITS DIRECTLY TO THE EXTERIOR OF THE |
| | BUILDING; HOWEVER, THE OVERALL FLOOR PLAN LOCATED ON |
| | SHEET A-1.0 INDICATES INTERIOR STAIR DISCHARGE. |
| | |
| | REPEAT COMMENT:SMOKE OR FIRE-RATED WALLS SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | REPEAT COMMENT: PROVIDE SMOKE DETECTION FOR ELEVATOR |
| | LOBBY RECALL OPERATIONS. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |