| 2012-04-18 13:06:35 | BUILDING PLAN REVIEW |
| | PERMIT: 12030123 |
| | ADD: 401 S DIXIE HWY |
| | CONT: TBD |
| | TEL: (561)366-8286 |
| | |
| | 2010 FLORIDA BUILDING CODE W/ |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. [B] 302.1 |
| | EXISTING BUILDINGS OR STRUCTURES. ADDITIONS OR |
| | ALTERATIONS TO ANY BUILDING OR STRUCTURE SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | BUILDING FOR NEW CONSTRUCTION. ADDITIONS OR ALTERATIONS |
| | SHALL NOT BE MADE TO AN EXISTING BUILDING OR STRUCTURE |
| | THAT WILL CAUSE THE EXISTING BUILDING OR STRUCTURE TO |
| | BE IN VIOLATION OF ANY PROVISIONS OF THE FLORIDA |
| | BUILDING CODE, BUILDING |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE: SHEET A-1.0 INDICATES AN EXISTING VERTICAL EXIT |
| | STAIR THAT LEADS INTO A LOBBY, NOT TO A EXIT PASSAGE |
| | WAY OR EXIT DISCHARGE. PLEASE REVIEW THE COVERSHEET |
| | CS-1 THE KEY MAP THAT SHOWS AN EXIT PASSAGEWAY TO THE |
| | EXIT DISCHARGE. 2007/09 EXISTING BUILDING CODE [B] |
| | 302.1 EXISTING BUILDINGS OR STRUCTURES. ADDITIONS OR |
| | ALTERATIONS TO ANY BUILDING OR STRUCTURE SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | BUILDING FOR NEW CONSTRUCTION. ADDITIONS OR ALTERATIONS |
| | SHALL NOT BE MADE TO AN EXISTING BUILDING OR STRUCTURE |
| | THAT WILL CAUSE THE EXISTING BUILDING OR STRUCTURE TO |
| | BE IN VIOLATION OF ANY PROVISIONS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1) COMPLIED. |
| | |
| | 2)SHEET A-1.0 INDICATES THE INSTALATION OF NEW EXTERIOR |
| | BI-PARTING DOORS AND OR NEW BI-PATING DOORS WITH SIDE |
| | LIGHTS AND NEW WINDOWS. |
| | FBC-B 1609 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. BI-PARTING DOORS. |
| | (B) WINDOWS -HIGHLIGHT TYPE OF GLAZING TO BE INSTALLED, |
| | MULLION REPORT INCLUDED IN WINDOW NOA LENGHT IS GOOD |
| | FOR ONLY 120 INCHES OR 10 FT. PLANS INDICATE THE |
| | HORIZONTAL MULLION WILL NEED TO SPAN 15'-5". |
| | C) MULLIONS |
| | |
| | 3) NEW COMMENT: MISSING WIND DESIGN, PLANS SUBMITTED |
| | AFTER MARCH 14/ 2012 ARE TO BE DESIGNED TO THE 2010 |
| | FBC-B AND ASCE 7-10 PLEASE PROVIDE WIND ZONE AAND |
| | ASSOCIATED PRESSURES V (ULT). FBC-B 1609. |
| | |
| | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) SHEET A-2.0 DETAIL DOOR TYPE B3 THE BIPARTING DOORS |
| | AND TRANSOM ABOVE, WHAT TYPE OF STRUCTURAL MEMBER WILL |
| | BE LOCATED BETWEEN THE BI-PARTING DOORS AND TRANSOM |
| | WINDOWS ABOVE? HOW WILL IT BE ANCHORED INTO THE MAIN |
| | WIND FORCE RESISTING SYSTEM? PROVIDE ADDITIONAL PRODUCT |
| | APPROVAL FOR MULLION OR FRAMING, BEAM SUPPORT. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) SHEET S-2 GLASS & ALUMINUM FRAME CANOPY DESIGGN, |
| | FABRICATION AND ASSEMBLY SHALL CONFORM TO AAASM 35 AND |
| | SPECIFICATIONS FOR ALUMINUM STRUCTURES. |
| | |
| | 9) SHEET S-2GLAZING IN SLOPED ASSEMBLIES SHALL COMPLY |
| | WITH FBC-B 2405.2 ALLOWABLE GLAZING MATERIALS AND |
| | LIMITATIONS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |