Date Text
2012-03-15 15:39:251. PROPOSED CANOPY SHALL PROJECT A MINIMUM OF 8 FEET
 FROM THE BUILDING FACADE.
 2. PLEASE INDICATE THE CANOPY VERTICAL CLEARANCE FROM
 SIDEWALK. MINIMUM 10 FEET VERTICAL CLEARANCE SHALL BE
 PROVIDED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.