| Plan Review Notes For Permit 12030118 |
| Permit Number |
12030118 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-14 10:13:49 | PLANS DENIED | | | 1) EQUIPMENT SUBMITTAL SUBMITTED WITH THE PLANS DO NOT | | | MATCH | | | EQUIPMENT SCHEDULE ON THE PLANS .SECTION 106.3 2007 FBC | | | 2) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER | | | CONTROLS | | | FOR FRESH AIR 2007 ENERGY CODE. | | | 3) CONDENSER UNIT DETAIL ON PAGE AC-1 DOES NOT SHOW THE | | | SIZE BOLT USED FOR THE TIE DOWN.301.12 WIND RESISTANCE | | | 2007 FBC (M) | | | 4) PROVIDE A DETAIL ON THE PLANS SHOWING EQUIPMENT RACK | | | TIE DOWN TO ROOF SECTION 301.12 WIND RESISTANCE 2007 | | | FBC (M) | | | 5) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS AND | | | 606.4.1 | | | SUPERVISION 2007 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | | | | |
|