Plan Review Notes
Plan Review Notes For Permit 12030118
Permit Number 12030118
Review Stop M
Sequence Number 1
Notes
Date Text
2012-03-14 10:13:49PLANS DENIED
 1) EQUIPMENT SUBMITTAL SUBMITTED WITH THE PLANS DO NOT
 MATCH
 EQUIPMENT SCHEDULE ON THE PLANS .SECTION 106.3 2007 FBC
 2) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROLS
 FOR FRESH AIR 2007 ENERGY CODE.
 3) CONDENSER UNIT DETAIL ON PAGE AC-1 DOES NOT SHOW THE
 SIZE BOLT USED FOR THE TIE DOWN.301.12 WIND RESISTANCE
 2007 FBC (M)
 4) PROVIDE A DETAIL ON THE PLANS SHOWING EQUIPMENT RACK
 TIE DOWN TO ROOF SECTION 301.12 WIND RESISTANCE 2007
 FBC (M)
 5) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS AND
 606.4.1
 SUPERVISION 2007 FBC (M)