Plan Review Notes
Plan Review Notes For Permit 12030118
Permit Number 12030118
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-03-08 12:40:01301 CLEMATIS STREET - SUITE #107
 PERMIT #12030118
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING
 OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE
 EXTINGUISHER COMPANY.
  
 A MAXIMUM OCCUPANT LOAD SIGN OF 49 PERSONS NEEDED TO BE
 CONSPICUOUSLY POSTED IN THE CUSTOMER SEATING AREA. THE
 MAXIMUM OCCUPANT LOAD INCLUDES INDOOR SEATING AND ANY
 FUTURE OUTSIDE SEATING.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE/SMOKE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 INDICATE LOCATIONS OF EXISTING FIRE ALARM NOTIFICATION
 APPLIANCES.
  
 NO FIRE SPRINKLER PROTECTION IS SHOWN IN THE WATER
 HEATER CLOSET OR SPRINKLER RISER ROOM.
  
 AN ADDITIONAL SPRINKLER IS NEEDED IN THE DRY STORAGE
 AREA TO ACCOUNT THE FOR THE COLUMN OBSTRUCTION.
  
 THE LOCATION OF THE NEW WALLS IN THE STAFF PREP AREA
 MAY RESULT IN RELOCATED SPRINKLERS TO PROVIDE PROPER
 COVERAGE.
  
 IF NOT ALREADY EXISTING, PROVIDE THE FOLLOWING:
 1) CHAIN WITH LOCK FOR SUPERVISING THE BACKFLOW
 PREVENTER IN THE OPEN POSITION.
 2) LOCKING KNOX CAPS ON FIRE DEPARTMENT CONNECTION.
 3) REFLECTIVE, WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION LOCATION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  