| 2012-04-25 17:14:18 | 12030117 |
| | 1016 CLARE AVE. #4 |
| | INTERIOR REMODEL FOR INDOOR SOCCER |
| | |
| | PLEASE SUBMIT AN ELECTRICAL PLAN. |
| | |
| | INCLUDE A RISER PLAN SHOWING THE NEW AND EXISTING |
| | ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECT, |
| | SERVICE GROUNDING, CONDUIT SIZE AND TYPE, VOLTAGE, |
| | CONDUCTOR SIZE AND TYPE ALL LOCATED ON THE PLAN. |
| | INCLUDE A SUMMARY LOAD CALCULATION SHOWING EXISTING |
| | ELECTRIC SERVICE CAN HANDLE THE NEW LOADS; VERIFY |
| | SAFETY CLEARANCES AND ACCESS. NEC 110.26, 215.5 |
| | PROVIDE PANEL SCHEDULES SHOWING RATING, SIZE AND WIRING |
| | METHOD FOR THE NEW ELECTRICAL CIRCUITS. NEC 210.3 |
| | SHOW SERVICE LOCATION ON THE PLAN. NEC 230.72 |
| | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE |
| | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES |
| | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL |
| | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, |
| | EXISTING BUILDING CODE 711.1 |
| | PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94 |
| | PROVIDE FOR GFCI PROTECTION FOR ANY PROPOSED VENDING |
| | MACHINES. NEC 422.51 |
| | GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN |
| | BATHROOMS, OUTDOORS, AND ADJACENT TO SINKS. NEC 210.8 |
| | PROVIDE SPECIFICATIONS ON LIGHT FIXTURES SHOWING |
| | PROTECTION AGAINST DAMAGE. LUMINAIRES SUBJECT TO |
| | PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS AND |
| | SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM DAMAGE. |
| | NEC 410.10(E) |
| | VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED |
| | WORKING SPACE HAS BEEN PROVIDED FOR THE ELECTRICAL |
| | EQUIPMENT AND PANEL BOARDS. NEC 110.26, 240.24, 408.17 |
| | PROVIDE A MECHANISM TO GUARD THE PANEL BOARDS TO |
| | PREVENT PHYSICAL DAMAGE IF LOCATED NEAR THE PLAYING |
| | FIELDS. NEC 110.27 |
| | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| | ALARM SYSTEM, VOICE AND DATA. |
| | |