| Notes |
| Date |
Text |
| 2012-03-14 12:21:19 | PLANS DENIED | | | 1) PROVIDE PRODUCT APPROVALS FOR OUTSIDE AIR GRILLE, | | | AND SIZE OF GRILLE. | | | SECTION 106.3 FBC. | | | 2) ELEVATOR EQUIPMENT ROOM AND STORAGE ROOM SHOW NEW | | | DUCT | | | PROVIDE DUCT AND GRILLE SIZE ON THE PLANS | | | 3) PROVIDE TWO COPIES OF THE MANUFACTURERS INSTALLATION | | | INSTRUCTIONS ON | | | THE FIRE DAMPERS WITH THE PLANS 304.1 GENERAL 2007 FBC | | | (M) | | | 4) REFER TO SECTION 601.4 BALANCED RETURN AIR EXCEPTION | | | #3 FOR | | | STORAGE ROOM. | | | 5) REFER TO SECTION 601.4 BALANCED RETURN AIR FOR LOBBY | | | 2007 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|