| Plan Review Notes For Permit 12030117 |
| Permit Number |
12030117 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-09 13:23:01 | 1016 CLARE AVENUE - SUITE #4 | | | PERMIT #12030117 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PLANS INDICATE THE USE OF FIRE RATED GYPSUM BOARD | | | FOR ALL NEW PARTITIONS. ARE ALL OPENINGS AND | | | PENETRATIONS INTENDED TO BE PROTECTED? | | | | | | INDICATE EXISTING WALLS THAT HAVE A FIRE RATING WITH | | | PROTECTED OPENINGS AND PENETRATIONS. | | | | | | ALL FIRE RATED DOORS SHALL BE SELF CLOSING AND POSITIVE | | | LATCHING. | | | | | | PROVIDE A PERMANENT SIGN ON THE CORRIDOR DOOR OF THE | | | FIRE ROOM INDICATING "FACP" AND "SPR RISER". | | | | | | FIRE SPRINKLERS WILL NEED TO BE ADDED/RELOCATED TO | | | ACCOUNT FOR THE NEW ROOMS AND NEW WALL LOCATIONS. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|