Plan Review Notes
Plan Review Notes For Permit 12030104
Permit Number 12030104
Review Stop Z
Sequence Number 1
Notes
Date Text
2012-03-13 12:07:11FAILED
  
 PLEASE RESPOND IN WRITING.
  
 1) PLEASE VERIFY THAT NO CHANGES ARE BEING MADE THE
 EXTERIOR FACADE OF THE BUILDING.
  
 2) THE PLANS SHOW THE INSTALLATION OF NEW ROOF MOUNTED
 EQUIPMENT. THE CITYPLACE DRI REQUIRES THAT ALL ROOFTOP
 MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH
 ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW. PLEASE PROVIDE
 DETAILS ON HOW THE NEW ROOFTOP EQUIPMENT WILL BE
 SCREENED. THE HEIGHT OF THE EQUIPMENT AND THE HEIGHT OF
 THE SCREENING SHALL BE PROVIDED.
  
 3) THE PLANS SHOW A 120 GALLON LP TANK ON THE NORTH
 SIDE OF THE BUILDING ADJACENT TO THE ALLEY. IS THIS
 TANK PROPOSED TO BE ABOVE OR BELOW GRADE? IF ABOVE
 GRADE THEN IT SHALL BE SCREENED FROM PUBLIC VIEW IN
 ACCORDANCE WITH THE CITYPLACE DRI REQUIREMENTS. THE
 SITE PLAN SHOWS LANDSCAPE AT THIS LOCATION THAT WOULD
 HAVE TO BE REMOVED FOR THE INSTALLATION OF A TANK.
 PLEASE CLARIFY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.