| 2012-03-23 09:00:38 | PLANS DENIED | | | 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB | | | ADAPTER TO CURB TIE DOWN | | | AND UNIT TO CURB TIE DOWN PER SECTION 301.21 WIND | | | RESISTANCE 2007 FBC (M) | | | 2) REFER TO SECTION 304.10 GUARDS 2007 FBC (M) | | | 3) SEPARATE APPLICATION, PLANS AND PERMIT REQUIRED FOR | | | REFRIGERATION & COOLERS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|