Plan Review Notes
Plan Review Notes For Permit 12030104
Permit Number 12030104
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-14 08:57:27BUILDING PLAN REVIEW
 PERMIT: 12030104
 ADD: 375 S ROSEMARY AVE
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION:
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 PLEASE PROVIDE BY FIRST BUILDING INSPECTION;
  
 1) SHEET S-2 DETAILS 1 & 2 BOTH INDICATE THE USE OF
 STEEL TIE DOWN STRAPS, NO MANUFACTURER NOR PRODUCT
 MODEL NUMBER IS PROVIDED. THE PLANS INDICATE IN BOTH OF
 THESE DETAILS TRIPLE THICK ENDS, DETAIL # 2 INDICATES
 TO FOLD THE ENDS. PLEASE PROVIDE APPROVAL FROM THE
 MANUFACTURER FOR USE OF THERE PRODUCT IN THIS MANNER.
 SIMPSON IN THEIR LITERATURE
 HAS TWO AREAS WHERE THEY SPECIFICALLY WARN AGAINST THIS
 PRACTICE. IN SMPSONS 2011-2012 CATALOG PAGE 21 UNDER
 THE IMPORTANT INFORMATION & GENERAL NOTES:
 1) WARNING # 4 ONLY BEND PRODUCTS THAT ARE SPECIFICALLY
 DESIGNED TO BE BENT.
 2) HEADING GENERAL NOTES (I) UNLESS OTHERWISE NOTED,
 BENDING STEEL IN THE FIELD MAY CAUSE FRACTURES AT THE
 BEND LINE. FRACTURED STEEL WILL NOT CARRY LOAD AND MUST
 BE REPLACED.
  
 2) SHEET S-2 DETAIL # 2 IT IS NOT CLEAR IF THE STRAP IS
 A SINGLE STRAP THAT BOLTS INTO THE BENCH BEAM IS A
 CONTINUAL STRAP UP OVER THE A/C COMPRESSOR AND THE
 OTHER END ATTACHING TO THE OPPOSITE SIDE OF THE BENCH
 BEAM? OR ARE THE FASTENERS TO THE CONDENSING UNIT
 MISSING THE FASTENER TYPE?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER