| 2012-03-14 08:57:27 | BUILDING PLAN REVIEW |
| | PERMIT: 12030104 |
| | ADD: 375 S ROSEMARY AVE |
| | CONT: OAK CONSTRUCTION |
| | TEL: (954)583-9625 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | PLEASE PROVIDE BY FIRST BUILDING INSPECTION; |
| | |
| | 1) SHEET S-2 DETAILS 1 & 2 BOTH INDICATE THE USE OF |
| | STEEL TIE DOWN STRAPS, NO MANUFACTURER NOR PRODUCT |
| | MODEL NUMBER IS PROVIDED. THE PLANS INDICATE IN BOTH OF |
| | THESE DETAILS TRIPLE THICK ENDS, DETAIL # 2 INDICATES |
| | TO FOLD THE ENDS. PLEASE PROVIDE APPROVAL FROM THE |
| | MANUFACTURER FOR USE OF THERE PRODUCT IN THIS MANNER. |
| | SIMPSON IN THEIR LITERATURE |
| | HAS TWO AREAS WHERE THEY SPECIFICALLY WARN AGAINST THIS |
| | PRACTICE. IN SMPSONS 2011-2012 CATALOG PAGE 21 UNDER |
| | THE IMPORTANT INFORMATION & GENERAL NOTES: |
| | 1) WARNING # 4 ONLY BEND PRODUCTS THAT ARE SPECIFICALLY |
| | DESIGNED TO BE BENT. |
| | 2) HEADING GENERAL NOTES (I) UNLESS OTHERWISE NOTED, |
| | BENDING STEEL IN THE FIELD MAY CAUSE FRACTURES AT THE |
| | BEND LINE. FRACTURED STEEL WILL NOT CARRY LOAD AND MUST |
| | BE REPLACED. |
| | |
| | 2) SHEET S-2 DETAIL # 2 IT IS NOT CLEAR IF THE STRAP IS |
| | A SINGLE STRAP THAT BOLTS INTO THE BENCH BEAM IS A |
| | CONTINUAL STRAP UP OVER THE A/C COMPRESSOR AND THE |
| | OTHER END ATTACHING TO THE OPPOSITE SIDE OF THE BENCH |
| | BEAM? OR ARE THE FASTENERS TO THE CONDENSING UNIT |
| | MISSING THE FASTENER TYPE? |
| | |