| Plan Review Notes For Permit 12030094 |
| Permit Number |
12030094 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-08 13:08:23 | 12030094 | | | 1449 8TH ST. | | | INTERIOR RENOVATION | | | | | | PROVIDE AN ELECTRIC SERVICE RISER PLAN WITH WIRE SIZES, | | | GROUNDING ETC. INDICATE THE LOCATION OF THE SERVICE. | | | SHOW LOCATION OF MAIN BREAKER AND METER. NEC 215.15 | | | THE MAIN SERVICE DISCONNECT MUST BE LOCATED NEAREST THE | | | POINT OF ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | FOR THE NEW WALL SPACES ADD RECEPTACLES SO THAT NO WALL | | | SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE AND ALL | | | WALL SPACES MORE THAN 2 FEET IN WIDTH HAVE A RECEPTACLE | | | I.E. NEW CLOSET WALL. NEC 210.52 | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. 2008 NEC 250.94 | | | ALL NEW RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC | | | 406.11 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|