| Date |
Text |
| 2012-07-23 17:07:42 | FAILED |
| | |
| | PLEASE PROVIDE RESPONSES IN WRITING: |
| | |
| | A) REPEAT COMMENT: THE FOLLOWING CONDITIONS OF THE SITE |
| | PLAN APPROVAL FOR THIS BUILDING HAVE NOT BEEN |
| | SATISFIED: |
| | |
| | 1) PRIOR TO THE SUBMITTAL FOR A BUILDING PERMIT, THE |
| | APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY |
| | AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY'S POLICE |
| | DEPARTMENT CRIME PREVENTION THROUGH ENVIRONMENTAL |
| | DESIGN ("CPTED") OFFICIAL. |
| | |
| | A) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF |
| | CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY |
| | MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR |
| | THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE |
| | LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL, |
| | VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS, |
| | REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE |
| | SUB-CONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF |
| | WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO |
| | PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT. |
| | |
| | B) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED |
| | THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT. |
| | NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A |
| | STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT. |
| | |
| | B) REPEAT COMMENT: PRIOR TO ZONING APPROVAL OF THIS |
| | PERMIT, A SEPARATE LANDSCAPE PERMIT AND SITE PERMIT, TO |
| | INCLUDE THE PARKING STRIPING, SHALL BE SUBMITTED TO THE |
| | BUILDING DIVISION. |
| | |
| | C) REPEAT COMMENT: THE CHANGES TO THE KARLAN BUILDING |
| | FOR THE SERVICE CANOPIES (SHEET SC101) AND OTHER MINOR |
| | SITE CHANGES REQUIRE THE APPROVAL OF A MINOR SITE PLAN |
| | AMENDMENT FOR THE CHANGES TO THE LAYOUT OF THE SITE. A |
| | REVISED LANDSCAPE PLAN, SHOWING THE RELOCATION OF THE |
| | TREES WITHIN THE LIMITS OF WORK IS ALSO REQUIRED AS |
| | PART OF THE MINOR AMENDMENT. UPDATE - A MINOR AMENDMET |
| | HAS BEEN SUBMITTED BUT IT IS NOT SUFFICIENT. |
| | |
| | D) SHEET L102 DOES NOT SHOW THE LATEST SITE DATA TABLES |
| | (SPECIFICALLY THE BUILDING DATA TABLE). IT APPEARS THAT |
| | IT IS BASED ON AN OLDER PLAN. |
| | |
| | E) THE PARKING DETAILS ON SHEET L 104 DO NOT MATCH THE |
| | PARKING SPACES SHOWN ON THE CIVIL DRAWINGS (BOTH |
| | DETAILS AND PLANS). |
| | |
| | F) REPEAT COMMENT SHOW THE ROOFTOP MECHANICAL EQUIPMENT |
| | ON THE ELEVATIONS TO SHOW HOW IT WILL BE SCREENED. THE |
| | A/C UNITS ON TOP OF THE CURBS APPEAR TO BE 5 FEET HIGH, |
| | WITH A LOWER PARAPET. THIS DOES NOT APPLY TO THE |
| | COOLING TOWERS, WHICH ARE SHOWN AS SCREENED. |
| | |
| | G) REPEAT COMMENT - THE APPROVED ELEVATIONS OF THE |
| | GENERATOR BUILDING DID NOT INCLUDE GRILLS FOR THE VENTS |
| | FACING MILITARY TRAIL. THE WALL AND LANDSCAPE DO NOT |
| | PROVIDE ADEQUATE BUFFER FOR THE PROPOSED ELEVATION. |
| | |
| | H) THE NECESSARY DOCUMENTS SHALL BE SUPPLIED TO THE |
| | PLANNING DIVISION TO SECURE AN APPROVED TREE ALTERATION |
| | PERMIT. |
| | |
| | I) SEPARATE PERMITS ARE REQUIRED FOR LANDSCAPE, PARKING |
| | STRIPING, FENCING, SITE/LANDSCAPE LIGHTING AND SIGNAGE. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |