| Date |
Text |
| 2012-03-27 18:33:11 | FAILED |
| | |
| | PLEASE PROVIDE RESPONSES IN WRITING: |
| | |
| | A) THE FOLLOWING CONDITIONS OF THE SITE PLAN APPROVAL |
| | FOR THIS BUILDING HAVE NOT BEEN SATISFIED: |
| | |
| | 1) PRIOR TO THE SUBMITTAL FOR A BUILDING PERMIT, THE |
| | APPLICANT SHALL: |
| | |
| | A. SECURE AN APPROVED TREE ALTERATION PERMIT FROM THE |
| | PLANNING DIVISION. |
| | |
| | B. PREPARE A CONSTRUCTION SITE SECURITY AND MANAGEMENT |
| | PLAN FOR APPROVAL BY THE CITY'S POLICE DEPARTMENT CRIME |
| | PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED") |
| | OFFICIAL. |
| | |
| | I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF |
| | CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY |
| | MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR |
| | THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE |
| | LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL, |
| | VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS, |
| | REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE |
| | SUB-CONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF |
| | WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO |
| | PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT. |
| | |
| | II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED |
| | THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT. |
| | NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A |
| | STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT. |
| | |
| | 2) THE APPLICANT SHALL SUBMIT THE FOLLOWING ITEMS AT |
| | THE TIME OF BUILDING PERMIT APPLICATION: |
| | |
| | A. A COPY OF THE PERMIT MODIFICATION FROM THE SOUTH |
| | FLORIDA WATER MANAGEMENT DISTRICT AND NORTHERN PALM |
| | BEACH COUNTY IMPROVEMENT DISTRICT AND SIGNED AND SEALED |
| | DRAINAGE CALCULATIONS TO THE ENGINEERING SERVICES |
| | DEPARTMENT. |
| | |
| | B) PRIOR TO ZONING APPROVAL OF THIS PERMIT, A SEPARATE |
| | LANDSCAPE PERMIT AND SITE PERMIT, TO INCLUDE THE |
| | PARKING STRIPING, SHALL BE SUBMITTED TO THE BUILDING |
| | DIVISION. |
| | |
| | C) THE CHANGES TO THE KAPLAN BUILDING FOR THE SERVICE |
| | CANOPIES (SHEET SC101) REQUIRE THE APPROVAL OF A MINOR |
| | SITE PLAN AMENDMENT FOR THE CHANGES TO THE LAYOUT OF |
| | THE SITE. A REVISED LANDSCAPE PLAN, SHOWING THE |
| | RELOCATION OF THE TREES WITHIN THE LIMITS OF WORK IS |
| | ALSO REQUIRED AS PART OF THE MINOR AMENDMENT. |
| | |
| | D) THE SURVEY PROVIDED DOES NOT COVER THE ENTIRE WORK |
| | AREA FOR THE KAPLAN BUILDING CANOPIES. |
| | |
| | E) THE PLANS HAVE BEEN CHANGED FROM THE APPROVED PLANS |
| | AS FOLLOWS AND REQUIRE THE APPROVAL OF A MINOR SITE |
| | PLAN AMENDMENT: |
| | |
| | A. THE ENTRY DRIVE HAS BEEN WIDENED BY 5 FEET, |
| | RESULTING IN A REDUCTION IN THE TERMINAL ISLAND SIZE. |
| | |
| | B. THE ENTRY MEDIAN INCREASED FROM 189 TO 195 FEET. |
| | PLEASE VERIFY THAT THE TURNING RADII STILL WORK INTO |
| | THE SITE. |
| | |
| | F) THE PLANS STATE THAT THE CIVIL PLANS ARE BEING USED |
| | FOR CONSTRUCTION; THEREFORE THE BICYCLE RACK DIMENSIONS |
| | SHALL BE SHOWN ON SHEET C-7 AND A BICYCLE RACK DETAIL |
| | SHALL BE PROVIDED (AS SHOWN ON SHEET L104). |
| | |
| | G) THE NEW PARKING AREAS AT THE SOUTH END OF THE SITE |
| | STATE THAT WHEEL STOPS WILL BE USED WITH THE 2 FOOT |
| | OVERHANG. THIS IS NOT PERMITTED, AS THEY WILL NOT STAY |
| | IN PLACE. A D-CURB IS REQUIRED. THE PARKING DETAIL |
| | SHOWS THIS CONDITION AS WELL AND SHALL BE AMENDED. |
| | NOTE: THE ADA SPACES OVERHANG PAVING AND THUS MAY |
| | REMAIN AS SHOWN ON THE DETAIL. |
| | |
| | H) SHOW THE MECHANICAL EQUIPMENT ON THE ELEVATIONS TO |
| | SHOW HOW IT WILL BE SCREENED. THE A/C UNITS ON TOP OF |
| | THE CURBS APPEAR TO BE 5 FEET HIGH, WITH A LOWER |
| | PARAPET. THIS DOES NOT APPLY TO THE COOLING TOWERS, |
| | WHICH ARE SHOWN AS SCREENED. |
| | |
| | I) THE APPROVED ELEVATIONS OF THE GENERATOR BUILDING |
| | DID NOT INCLUDE GRILLS FOR THE VENTS FACING MILITARY |
| | TRAIL. THE WALL AND LANDSCAPE DO NOT PROVIDE ADEQUATE |
| | BUFFER FOR THE PROPOSED ELEVATION. |
| | |
| | J) SEPARATE PERMITS ARE REQUIRED FOR FENCING, |
| | SITE/LANDSCAPE LIGHTING AND SIGNAGE. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |