| 2012-03-30 15:53:42 | 12030044 |
| | 4847 FRED GLADSTONE DR. |
| | TYPE IIIA 3 STORY BUILDING |
| | INSTITUTIONAL GROUP I-2 |
| | |
| | E000 |
| | UPDATE THE PLAN WITH A LEGEND AND GENERAL NOTES. |
| | INCLUDE A CONDUIT SCHEDULE FOR BRANCH CIRCUITS AND |
| | FEEDERS |
| | E001 |
| | PLEASE CLARIFY THE FEEDER SIZE PROPOSED FOR ATS ?LS. |
| | BOTH 250 KCMIL AND 500KCMIL HAVE BEEN PROPOSED. |
| | CLARIFY HOW THE GENERATOR QUICK CONNECT WILL FUNCTION |
| | SAFELY. |
| | E102 |
| | CLARIFY THE USE OF ALUMINUM EQUIPMENT GROUNDING |
| | CONDUCTORS. THE GENERAL RULE SUGGESTS THAT GROUNDING |
| | CONDUCTORS WHICH FACILITATE THE BONDING OF PANEL BOARDS |
| | SHOULD BE COPPER. NEC 517.11 |
| | E002 |
| | PROVIDE SERVICE RISER SPECIFICATION FOR GUARD SHACK |
| | TRANSFORMER AND PANEL EQLGS. PROVIDE GROUND ROD AND |
| | NEUTRAL TO BOND AT GUARD SHACK. |
| | CLARIFY/COORDINATE AND UPDATE THE RISER PLAN AND PANEL |
| | SCHEDULES FOR THE FEEDER AND LOADS FOR THE KITCHEN |
| | PANEL EQLB1. |
| | NEC 215.5 |
| | E003 |
| | VERIFY THE 112 ? KVA TRANSFORMERS OR LARGER ARE LOCATED |
| | WITHIN FIRE-RESISTANT ROOMS WITH A ONE HOUR FIRE RATING |
| | OR COMPLY WITH THE NEC EXCEPTIONS. NEC 450.21 (B) |
| | E203 |
| | A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR |
| | EQUIPMENT ROOMS. NEC 620.23 |
| | E501A |
| | FIRE PUMP ROOM REQUIRES A 2 HOUR FIRE RATING. FBC |
| | 420.3.19 |
| | VERIFY ALL CIRCUIT CONDUCTORS AND CONTROL WIRING FOR |
| | THE FIRE PUMP AND GENERATOR ARE INDEPENDENT AND HAVE A |
| | MINIMUM OF 2 HOUR AND 1 HOUR FIRE PROTECTION |
| | RESPECTIVELY. NEC 695.6, 605.14 |
| | E600 |
| | PROVIDE A DETAIL WHICH ILLUSTRATES THE REQUIRED WORKING |
| | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN |
| | PROVIDED AS REQUIRED FOR THE ELECTRICAL EQUIPMENT AND |
| | PANEL BOARDS. NEC 110.26, 240.24, 408.17 |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL |
| | EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING |
| | THE SIZE AND TYPE OF HAZARDS. NEC 110.22, 110.16 |
| | E602 |
| | A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR |
| | EQUIPMENT ROOMS. NEC 620.23 |
| | E301A |
| | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. FBC 13-415 ABC.5 |
| | CLARIFY OR SUMMARIZE ON THE PLAN HOW THE LIGHTING WILL |
| | BE CONTROLLED USING MOTION SENSORS OR SIMILAR |
| | TECHNIQUES. SPACE CONTROL FBC 13-415 ABC.1.2. |
| | ADDITIONAL CONTROLS 13-415.ABC.1.3 |
| | P101 |
| | BUILDING DRAINS APPEAR TO CROSS THROUGH AND OVER THE |
| | ELECTRICAL EQUIPMENT WITHIN THE SPACE DEDICATED TO THE |
| | EQUIPMENT. NEC 110.26 (F) |
| | |
| | NOTE: |
| | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| | ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE |
| | AND DATA. |
| | A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING |
| | FOR POLES, BASES AND FIXTURES IS REQUIRED. |
| | |
| | ROBERT LECKY |
| | ELECTRIC PLANS EXAMINER |