| Plan Review Notes For Permit 12030017 |
| Permit Number |
12030017 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-13 16:42:16 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) BASED ON FBC TABLES R301.2(2) AND R301.2(3) FOR AN | | | OPENING 10 SQFT OR LESS AND A 30' MEAN ROOF HEIGHT THE | | | COMPONENT AND CLADDING PRESSURES ON THE ORIGINAL PLANS | | | ARE CORRECT. PLEASE SUBMIT SIGNED AND SEALED | | | CALCULATIONS THAT JUSTIFY THE LOWER PRESSURES. | | | | | | 2) THE PRODUCT APPROVAL FOR THE DOUBLE HUNG WINDOW | | | SPECIFIES DESIGN PRESSURES OF +55, -65 PSF. THE | | | REQUIRED NEGATIVE PRESSURE IN WALL ZONE 5 IS -66.08 PSF | | | USING THE TABLES SPECIFIED IN THE PREVIOUS COMMENT. | | | PLEASE CORRECT. FBC R301.2.1 | | | | | | 3) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED ARE FOR | | | A JOHNS-MANVILLE ROOFING PRODUCT (NOA NO 11-0126.01) | | | AND THE PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR A | | | GAF BUR SYSTEM (NOA NO 07-1219.09). PLEASE SUBMIT THE | | | CORRESPONDING PRODUCT APPROVAL. DCA RULE 9N-3 AND FBC | | | R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|