Plan Review Notes
Plan Review Notes For Permit 12030017
Permit Number 12030017
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-13 16:42:162007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) BASED ON FBC TABLES R301.2(2) AND R301.2(3) FOR AN
 OPENING 10 SQFT OR LESS AND A 30' MEAN ROOF HEIGHT THE
 COMPONENT AND CLADDING PRESSURES ON THE ORIGINAL PLANS
 ARE CORRECT. PLEASE SUBMIT SIGNED AND SEALED
 CALCULATIONS THAT JUSTIFY THE LOWER PRESSURES.
  
 2) THE PRODUCT APPROVAL FOR THE DOUBLE HUNG WINDOW
 SPECIFIES DESIGN PRESSURES OF +55, -65 PSF. THE
 REQUIRED NEGATIVE PRESSURE IN WALL ZONE 5 IS -66.08 PSF
 USING THE TABLES SPECIFIED IN THE PREVIOUS COMMENT.
 PLEASE CORRECT. FBC R301.2.1
  
 3) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED ARE FOR
 A JOHNS-MANVILLE ROOFING PRODUCT (NOA NO 11-0126.01)
 AND THE PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR A
 GAF BUR SYSTEM (NOA NO 07-1219.09). PLEASE SUBMIT THE
 CORRESPONDING PRODUCT APPROVAL. DCA RULE 9N-3 AND FBC
 R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]