| Notes |
| Date |
Text |
| 2012-03-02 16:28:26 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) PLEASE CLARIFY IF THIS AN EXACT CHANGE OUT OR WERE | | | DUCTS INSTALLED. PLEASE COMPLETE AN A/C CHANGE OUT FORM | | | IF THIS WAS AN EXACT CHANGE OUT. CITY AMENDMENTS | | | 106..1.1 | | | | | | 2) IF THIS IS A NEW INSTALLATION, SUBMIT TWO SETS OF | | | EQUIPMENT SIZING CALCULATIONS AND MECHANICAL PLANS WITH | | | EQUIPMENT SCHEDULE, DUCT LAYOUT WITH DUCT SIZES, GRILL | | | SIZES AND CFMS PER DROP SPECIFIED. CITY AMENDMENTS | | | 106.3.5.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|