| 2012-02-28 12:57:35 | 1901 NORTH FLAGLER DRIVE | | | PERMIT #12020630 | | | MASTER #11080026 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE QUALIFIED SYSTEM DESIGNER NEEDS TO PROVIDE A | | | SIGNATURE ON THE PLANS. | | | | | | PROVIDE THE CANDELA INTENSITY FOR THE VISUAL | | | NOTIFICATION APPLIANCES. | | | | | | PROVIDE ROOM NAMES/NUMBERS ON THE PLANS SO THE LOCATION | | | OF THE FIRE ALARM DEVICES CAN BE IDENTIFIED. | | | | | | PROVIDE BATTERY CALCULATIONS AS DEVICES HAVE BEEN ADDED | | | TO THE EXISTING NOTIFICATION APPLIANCE CIRCUIT. | | | | | | INDICATE WIRE GAGE. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|