| 2012-02-28 10:58:54 | 12020584 | | | 1300 8TH STREET | | | ELECTRIC SERVICE REPAIR | | | | | | THE ELECTRICAL RISER PLAN NEEDS TO SHOW THE MAIN | | | DISCONNECT SIZE, THE GROUNDING SYSTEM AND THE SERVICE | | | CONDUCTOR SIZE. INDICATE THE SIZE OF THE EXISTING PANEL | | | BOARD. AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE | | | MAIN SERVICE GROUND NEC 250.94, NEC 215.5 | | | | | | ROBERT LECKY | | | ELECTRIC PLAN REVIEWER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|