| Notes |
| Date |
Text |
| 2012-03-12 12:26:45 | PLANS DENIED | | | 1) DETAILS ON EXHAUST AND SUPPLY DO NOT MATCH NOTES | | | PAGE # 1 OF PLANS. | | | 2) PROVIDE ROD SIZE ON THE PLANS SUPPLY AIR CURB TO | | | UNISTRUT.PAGE 1 OF PLANS | | | 3) PAGE 1 OF PLANS SHOW JOIST PAGE 3 SHOWS RAFTERS. | | | 4) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS ON | | | WRAP ON TOP OF HOOD . | | | 5) REFER TO SECTION 304.10 GUARDS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | |
|