Plan Review Notes
Plan Review Notes For Permit 12020503
Permit Number 12020503
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-04-10 15:11:14515 NORTH FLAGLER DRIVE - SUITE #P100
 PERMIT #12020503
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 101, THE OCCUPANT LOAD IS CALCULATED BASED
 UPON THE USE (ASSEMBLY: EXERCISE W/ AND W/O EQUIPMENT)
 OF THE SPACE AND NOT THE OCCUPANCY CLASSIFICATION
 (BUSINESS).
  
 REPEAT COMMENT:THE OCCUPANT LOAD FACTOR FOR EXERCISE
 ROOMS WITH EQUIPMENT SHOULD BE 50 SQ.FT. PER PERSON AND
 15 SQ.FT. PER PERSON FOR EXERCISE ROOMS WITHOUT
 EQUIPMENT PER TABLE 7.3.1.2 OF NFPA 101.
  
 REPEAT COMMENT: THE BUILDING IS FUNCTIONING AS A
 MULTIUSE OCCUPANCY. INDICATE IF THE BUILDING IS
 DESIGNED FOR MIXED USE (NON-SEPARATED) OR SEPARATED USE
 PER SECTION 6.1.14.2.1 OF NFPA 101 FLORIDA EDITION
 2009. SEPARATED USE WILL REQUIRE A 1-HOUR FIRE BARRIER
 BETWEEN THE ASSEMBLY OCCUPANCY AND THE BUSINESS
 OCCUPANCY PER TABLE 6.1.14.4.1(B).
  
 REPEAT COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT
 HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE
 ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT
 FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 REPEAT COMMENT: FOR AN ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE.
  
 REPEAT COMMENT: PROVIDE THE NEW FIRE ALARM NOTIFICATION
 APPLIANCE LAYOUT. **NOTE - FA1.1 WAS NOT SUBMITTED**
  
 SHEET P1.1: PIPING APPEARS TO BE ROUTED THROUGH THE
 FIRE RATED EXIT PASSAGEWAY OF THE STAIR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE