| 2012-04-11 11:19:53 | BUILDING PLAN REVIEW |
| | PERMIT: 12020503 |
| | ADD: 515 N FLAGLER P-100 |
| | CONT: CUTTING EDGE BUILDING |
| | TEL: (561)282-8265 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) LIFE SAFETY SHEET LS-1: |
| | 1A) COMPLIED. |
| | |
| | 1B) 2ND REQUEST! THE CODE RESEARCH INDICATES THIS PLANS |
| | TO BE A BUSINESS OCCUPANCY, PLEASE SEE 303.1 A-3 |
| | GYMNASIUM WITHOUT SPECTATOR SEATING, IT APPEARS THIS |
| | MAY BE A CHANGE OF OCCUPANCY WHICH WOULD BE REVIEWED |
| | UNDER THE EXISTING BUILDING CODE 901.3.1 SECTION 912 OF |
| | THE EXISTING BUILDING CODE WOULD APPLY. |
| | |
| | 1C)2ND REQUEST! WITH THE A-3 OCCUPANCY THE OCCUPANT |
| | LOAD WILL CHANGE PLEASE SEE FBC-B TABLE 1004.1.1 |
| | EXERCISE ROOMS/ GYMASIUMS WITH EQUIPMENT 50 GROSS AND |
| | ROOMS WITHOUT EQUIPMENT 15 GROSS PLEASE MAKE THE |
| | REQUIRED OCCUPANT LOAD ADJUSTMENTS. |
| | RESPONSE INDICATES THAT THE SPACE WAS REDUCED TO 4934 |
| | SQ FT AN OCCUPANT LOAD OF 49. WHEN THERE IS A FRACTION |
| | ON AN OCCUPANT YOU ROUND UP NOT DOWN, MAKING THE |
| | OCCUPANT LOAD OF 50 UNDER A BUSINESS OCCUPANCY. |
| | |
| | BOAF INFORMAL INTERPRETATION 5484 HAS A SIMILAR |
| | ARGUEMENT DECLARING A BUSINESS OCCUPANCY BUT THEY WERE |
| | CORRECT IN THE BUSINESS OCCUPANCY CLASSIFICATION BUT |
| | THEY ALSO USED THE CORRECT OCCUPANT LOADING FROM TABLE |
| | 1004.1.1. IN YOUR CASE THE GYM (WITH EQUIPMENT) PORTION |
| | SHOULD BE TAKEN AT |
| | 50 GROSS AND THE AEROBATICS AT 15 GROSS. THIS COUNT |
| | WILL WELL PUT THE GYM ABOVE THE 50 OCCUPANT LOAD TO |
| | DECLARE THIS AN A-3 ASSEMBLY OCCUPANCY. |
| | |
| | BOAF INFORMAL INTERPRETATION 5662 PROVIDES A BIT OF |
| | HISTORY WHY THE FIGURES STATED ABOVE COME FROM, TO |
| | ALIGN THE FLORIDA BUILDING CODE WITH THE FLORIDA FIRE |
| | PREVENTION CODE, NFPA 101, TABLE 7.3.1.2. THE FFPC |
| | SUB-DIVIDES EVERCISE ROOMS INTO THE TWO CATEGORIES WITH |
| | AND WITHOUT EQUIPMENT. THE BASE CODE (IBC) SPECIFIES AN |
| | OLF OF 50 SQ FT GROSS PER PERSON. |
| | |
| | 1D) COMPLIED. |
| | |
| | 2) COMPLIED. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |