Plan Review Notes
Plan Review Notes For Permit 12020503
Permit Number 12020503
Review Stop B
Sequence Number 2
Notes
Date Text
2012-04-11 11:19:53BUILDING PLAN REVIEW
 PERMIT: 12020503
 ADD: 515 N FLAGLER P-100
 CONT: CUTTING EDGE BUILDING
 TEL: (561)282-8265
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET LS-1:
 1A) COMPLIED.
  
 1B) 2ND REQUEST! THE CODE RESEARCH INDICATES THIS PLANS
 TO BE A BUSINESS OCCUPANCY, PLEASE SEE 303.1 A-3
 GYMNASIUM WITHOUT SPECTATOR SEATING, IT APPEARS THIS
 MAY BE A CHANGE OF OCCUPANCY WHICH WOULD BE REVIEWED
 UNDER THE EXISTING BUILDING CODE 901.3.1 SECTION 912 OF
 THE EXISTING BUILDING CODE WOULD APPLY.
  
 1C)2ND REQUEST! WITH THE A-3 OCCUPANCY THE OCCUPANT
 LOAD WILL CHANGE PLEASE SEE FBC-B TABLE 1004.1.1
 EXERCISE ROOMS/ GYMASIUMS WITH EQUIPMENT 50 GROSS AND
 ROOMS WITHOUT EQUIPMENT 15 GROSS PLEASE MAKE THE
 REQUIRED OCCUPANT LOAD ADJUSTMENTS.
 RESPONSE INDICATES THAT THE SPACE WAS REDUCED TO 4934
 SQ FT AN OCCUPANT LOAD OF 49. WHEN THERE IS A FRACTION
 ON AN OCCUPANT YOU ROUND UP NOT DOWN, MAKING THE
 OCCUPANT LOAD OF 50 UNDER A BUSINESS OCCUPANCY.
  
 BOAF INFORMAL INTERPRETATION 5484 HAS A SIMILAR
 ARGUEMENT DECLARING A BUSINESS OCCUPANCY BUT THEY WERE
 CORRECT IN THE BUSINESS OCCUPANCY CLASSIFICATION BUT
 THEY ALSO USED THE CORRECT OCCUPANT LOADING FROM TABLE
 1004.1.1. IN YOUR CASE THE GYM (WITH EQUIPMENT) PORTION
 SHOULD BE TAKEN AT
 50 GROSS AND THE AEROBATICS AT 15 GROSS. THIS COUNT
 WILL WELL PUT THE GYM ABOVE THE 50 OCCUPANT LOAD TO
 DECLARE THIS AN A-3 ASSEMBLY OCCUPANCY.
  
 BOAF INFORMAL INTERPRETATION 5662 PROVIDES A BIT OF
 HISTORY WHY THE FIGURES STATED ABOVE COME FROM, TO
 ALIGN THE FLORIDA BUILDING CODE WITH THE FLORIDA FIRE
 PREVENTION CODE, NFPA 101, TABLE 7.3.1.2. THE FFPC
 SUB-DIVIDES EVERCISE ROOMS INTO THE TWO CATEGORIES WITH
 AND WITHOUT EQUIPMENT. THE BASE CODE (IBC) SPECIFIES AN
 OLF OF 50 SQ FT GROSS PER PERSON.
  
 1D) COMPLIED.
  
 2) COMPLIED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]