| Plan Review Notes For Permit 12020497 |
| Permit Number |
12020497 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-01 13:29:02 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | | AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | THE SHEET PROVIDED DOES NOT INCLUDE ALL REQUIRED | | | INFORMATION; SOME SAY "SEE ENGINEERING" FOR ANCHOR | | | SPACING BUT NO ENGINEERING PROVIDED. | | | | | | ON THE PRODUCT APPROVAL, ANCHOR SPACING FOR 43PSF | | | CIRCLED BUT SOME OPENINGS HAVE DESIGN PRESSURES GREATER | | | THAN -43. | | | | | | |
|