2012-07-19 19:14:02BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2007
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 COMMENT 3 FROM THE PREVIOUS REVIEW DATED 4/30/12 HAS
 NOT BEEN PROPERLY ADDRESSED.
 FBC 1609.1 WIND LOADS - THE "MANUFACTURER'S WIND LOAD
 TABLE" THAT WAS REFERENCED IN THE DAVID MILLER LETTER
 DATED 6/29/12, IS FOR A MULLION SO IT DOES NOT ADDRESS
 COMMENT 3 WHICH IS RELATED TO THE SIZE AND WIND LOAD
 RESISTANCE OF THE TRANSOM GLASS PANEL. THE NOA THAT WAS
 STAMPED AS REVIEWED BY DAVID MILLER ON 3/27/12 IS NOA#
 10-0511.04 AND THE GLASS LOAD CAPACITY TABLE ON SHEET 2
 SHOWS A MAXIMUM DLO WIDTH OF 52-1/4". ONLY ONE GLASS
 THICKNESS IS COVERED BY THE NOA AND IT IS 1/4" TEMPERED
 GLASS. COMMENT 3 STATES "THE GLASS SIZE IS NOMINAL 72"
 X 68" IN THE THE FIELD, WHICH EXCEEDS THE SIZE ON THE
 NOA". PLEASE PROVIDE A PRODUCT APPROVAL TO SHOW THAT
 THE TRANSOM GLASS PANEL CAN WITHSTAND THE DESIGN WIND
 PRESSURE GIVEN THE SIZE AND THICKNESS OF THE GLASS
 PANEL USED IN THE FIELD.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]