| 2012-02-23 09:57:41 | 319 CLEMATIS STREET | | | PERMIT #12020431 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | INDICATE THE LOCK/LATCH HARDWARE THAT WILL BE INSTALLED | | | ON THE DOORS. INDICATE HOW THE LOCK/LATCH WILL BE | | | RELEASED. THE LOCK/LATCH RELEASING MECHANISM ON ALL | | | DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE | | | RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE | | | AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED | | | UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE | | | SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND | | | SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR | | | TWISTING OF THE WRIST TO OPERATE. | | | | | | HURRICANE PROTECTION DEVICES ARE NOT PERMITTED ON | | | REQUIRED EXITS OF COMMERCIAL BUILDINGS PER SECTION | | | 7.3.4.1.1 OF NFPA 101 (FLORIDA EDITION). | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|