| Plan Review Notes For Permit 12020426 |
| Permit Number |
12020426 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-02-27 12:04:31 | RE-ROOF BUILDING REVIEW THIRD REVIEW COMMENTS. | | | | | | 1- ENGINEER TO REVISE RAS 117 CALCULATIONS. NAIL | | | ENHANCING FASTENING FOR ROOF ZONE #2 SUBMITTED IS THE | | | SAME AS FOR ROOF ZONE #1. THIS NAIL ENHANCING DOESN'T | | | MEET THE CALCULATED DESIGN PRESSURES. REVISE AS | | | REQUIRED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|