| Date |
Text |
| 2012-04-09 08:38:49 | 4801 DREHER TRAIL NORTH |
| | PERMIT #12020414 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET LS-100: UPDATE THE CODE LIST TO REFERENCE THE |
| | 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | DEMOLITION: TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED AREAS. ALL OTHER |
| | DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. |
| | |
| | DEMOLITION: WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| | DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| | EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| | MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY |
| | THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH |
| | DIXIE HIGHWAY. |
| | |
| | SHEET A-101: PROVIDE FIRE LANE SIGNAGE FOR EXISTING |
| | DROP-OFF LANE. FIRE LANES SHALL BE MARKED WITH |
| | FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY |
| | ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18" |
| | WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A |
| | MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE |
| | SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW |
| | AND BE SPACED A MAXIMUM OF 60 FEET APART. |
| | |
| | SHEET A-201: PROVIDE A 1-HOUR FIRE/SMOKE BARRIER FOR |
| | THE RECEIVING/STORAGE ROOM #105 PER SECTION 12.7.5.2 OF |
| | NFPA 101. PROTECT ALL OPENINGS AND PENETRATIONS. |
| | |
| | GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| | SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| | IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| | ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | GENERAL: FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 |
| | OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON |
| | DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| | LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| | PANIC HARDWARE. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: POST "NO SMOKING" SIGNS IN ALL EXHIBIT ROOMS. |
| | |
| | GENERAL: AN EMERGENCY PLAN SHALL BE DEVELOPED AND |
| | APPROVED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF |
| | OCCUPANCY. |
| | |
| | FIRE ALARM: A CERTIFICATE OF COMPLETION AND A THIRD |
| | PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE |
| | SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM |
| | INSPECTION. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |