| Plan Review Notes For Permit 12020414 |
| Permit Number |
12020414 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-09 11:09:00 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-201: INTAKE FOR OAU-1 IS LESS THAN 10 FEET | | | FROM THE LOADING DOCK AREA. MECHANICAL OUTDOOR AIR | | | INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET | | | HORIZONTALLY FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT | | | SOURCE, SUCH AS STREETS, ALLEYS, PARKING LOTS AND | | | LOADING DOCKS IN ACCORDANCE WITH FBC-M 401.4. SEE | | | DRAWING MARK-UP IN PROJECTDOX FOR EXACT LOCATION. | | | | | | 2. PAGE M-201: EF-T IS SHOWN WITH A CAPACITY OF 1500 | | | CFM AND DISCHARGING THROUGH AN 18X18 ROOF EXHAUST HOOD | | | WHICH IS SHOWN WITH A CAPACITY OF 250 CFM. PLEASE | | | COORDINATE EXHAUST FAN AND ROOF HOOD RATINGS TO ASSURE | | | PROPER VENTILATION RATES ARE PROVIDED IN ACCORDANCE | | | WITH FBC-M TABLE 403.3. SEE DRAWING MARK-UP IN | | | PROJECTDOX FOR EXACT LOCATION. | | | | | | 3. PROVIDE EVNTILATION CALCULATIONS FOR ALL NEWLY | | | CONSTRUCTED AND RENOVATED SPACES SHOWING OCCUPANCY | | | CLASSIFICATIOPN, OCCUPANT LOAD AND VENTILATION RATES IN | | | ACCORDANCE WITH FBC-M SECTION 403. | | | | | | 4. PROVIDE PRODUCT APPROVALS FOR ALL OUTSIDE LOUVERS | | | PER FAC RULE 9N-3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|