| Date |
Text |
| 2012-03-08 11:20:29 | BUILDING PLAN REVIEW |
| | PERMIT: 12020414 |
| | ADD: 4801 DREHER TRAIL N |
| | CONT: TBD |
| | TEL: (561)###-#### |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | BUILDING TYPE III-B |
| | FULLY SPRINKLERED |
| | |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-101 INDICATES DETAILS ON SHEET A-151 |
| | 1A) SHEET A-151 DETAIL # 1 INDICATES THE USE OF A |
| | PRE-MANUFACTURED ALUMINUM RAMP AND HANDRAIL NO DETAILS |
| | ARE PROVIDED FOR STRENGTH AN OR ACCESSIBILITY |
| | REQUIREMENTS |
| | |
| | 1B) SHEET A-151 DETAIL 02 INDICATES A CONCRETE RAMP AND |
| | HANDRAIL THE PLANS DO NOT PROVIDE ENOUGH INFORMATION |
| | FOR THE ACCESSIBLE RAMP NOR STAIRS. |
| | |
| | 1C) SHEET A-101 INDICATES A DETAIL 01/A151 WHICH REFERS |
| | TO DETAIL # 11/A-613. THE PLANS ARE NOT CLEAR AS TO IF |
| | THE HORIZONTAL AND VERTICAL CANOPY PIECES ARE TO BE |
| | SOLID OR DOES THE MATERIAL ALLOW WIND THROUGH THE |
| | MATERIAL. S-102 DOES INDICATE WITH NOTE 6 HIGHER |
| | PRESSURES FOR THIS CANOPY SECTION. |
| | |
| | 2) SHEET A-101 THIS LOCATION IS IN A A-7 FLOOD ZONE, |
| | THE MINIMUM FINISH FLOOR OF 12.5?. THE FINISH FLOOR OF |
| | THE EXISTING BUILDING AND ADDITION IS INDICATED WELL |
| | ABOVE THIS HEIGHT BUT THE |
| | NEW EMERGENCY GENERATOR AND PAD AS WELL AS HV/AC |
| | EQUIPMENT PAD HEIGHTS ARE NOT PROVIDED. THESE EQUIPMENT |
| | PADS HAVE TO BE AT LEAST THE BASE FLOOD ELEVATION OF |
| | 12.5 ? NGVD. |
| | |
| | 3) LS-100 HEADING BUILDING SEPARATION INDICATES THE |
| | BUILDING SEPARATION WALLS FIRE WALLS TO BE 3HOUR RATED |
| | WALLS AS WELL AS LS-201, LS-202 & LS-203 WITH 2 HOUR |
| | OPENING PROTECTIVE?S. |
| | |
| | 3A) PLEASE REVIEW 2007/09 FBC-B TABLE 705.4 FOOTNOTE C. |
| | FOR THE PURPOSES OF DETERMINING HEIGHT AND AREA IN |
| | ACCORDANCE WITH TABLE 503, FIRE WALLS DIVIDING |
| | BUILDINGS INTO SEPARATE BUILDINGS SHALL PROVIDE A |
| | 4-HOUR FIRE-RESISTANCE RATING. |
| | |
| | 3B) OPENING PROTECTIVES2007/09 FBC-B TABLE 715.4 |
| | REQUIRES EITHER A 3 HOUR RATED FIRE DOOR AND FIRE |
| | SHUTTER ASSEMBLY. PLEASE NOTE THAT 715.3 DOES ALLOW FOR |
| | 715.3 ALTERNATIVE METHODS FOR DETERMINING FIRE |
| | PROTECTION RATINGS. BASED ON THE FIRE EXPOSURE AND |
| | ACCEPTANCE CRITERIA SPECIFIED IN NFPA 252 OR NFPA 257. |
| | THE REQUIRED FIRE RESISTANCE OF AN OPENING PROTECTIVE |
| | SHALL BE PERMITTED TO BE ESTABLISHED BY ANY OF THE |
| | FOLLOWING METHODS OR PROCEDURES: |
| | 1. DESIGNS DOCUMENTED IN APPROVED SOURCES. |
| | 2. CALCULATIONS PERFORMED IN AN APPROVED MANNER. |
| | 3B) 3. ENGINEERING ANALYSIS BASED ON A COMPARISON OF |
| | OPENING PROTECTIVE DESIGNS HAVING FIRE-PROTECTION |
| | RATINGS AS DETERMINED BY THE TEST PROCEDURES SET FORTH |
| | IN NFPA 252 OR NFPA 257. |
| | 3B) 4. ALTERNATIVE PROTECTION METHODS AS ALLOWED BY |
| | SECTION 104.11. |
| | |
| | 4) SHEET LS-201, LS-202 & LS-203 ALL SHOW THE NEW DECK |
| | AND ADA MODULAR RAMP AS PART OF THE MEANS OF EGRESS BUT |
| | THE PLANS DO NOT PROVIDE COMPLIANCE WITH THE EXIT |
| | DISCHARGE LEADING TO A PUBLIC WAY. FBC-B 1024.1. |
| | 11-4.1.3(8)(II). |
| | |
| | 5) SHEET A-650 INDICATES WALL TYPES BUT NOTE # 3 |
| | INDICATES REFER TO LIFE SAFETY PLANS FOR LOCATION AND |
| | FULL EXTENT OF FIRE AND SMOKE RATED ASSEMBLIES. COMMENT |
| | # 3 DEALS WITH THE 4 HR RATED FIRE WALL THAT SEPARATES |
| | THE TWO BUILDINGS BUT THE PLANS DO NOT PROVIDE FOR FIRE |
| | RATING FOR THE FIRST FOUR FEET PAST WHERE THE EXTERIOR |
| | WALL INTERSECTS, SEE FBC-B 705.5.1. |
| | |
| | 6A) SHEET LS-201, LS-202 & LS-203 DOES NOT PROVIDE FOR |
| | ANY RATINGS OF OTHER WALLS. FBC-B TABLE 508.2 FOR |
| | STORAGE ROOMS WITH FULLY SPRINKLERED BUILDINGS STILL |
| | REQUIRE THE WALLS TO BE A SMOKE PARTITION SEE FBC- B |
| | 508.2.2.1. |
| | THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO THE |
| | UNDERSIDE OF THE FIRE-RESISTANCE-RATED FLOOR/CEILING |
| | ASSEMBLY OR FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY |
| | ABOVE OR TO THE UNDERSIDE OF THE FLOOR OR ROOF |
| | SHEATHING, OR SUB DECK ABOVE. |
| | |
| | 6B) SHEET A-251 DETAILS 03, 08 & 10 ARE ALL DETAILS |
| | INDICATING CUT SECTIONS THROUGH THE 4 HOUR FIRE RATED |
| | WALL, PLEASE PROVIDE AN ASSEMBLY RATING FOR SUCH WALL. |
| | SHEET A-611 DETAIL # 4 |
| | DEPICTS TWO SEPARATE WALL DETAILS DETAIL FOUND ON A-451 |
| | DETAIL # 5 DOES SHOW ROOF HEIGHTS AT TWO DIFFERENT |
| | HEIGHTS. PLEASE PROVIDE WALL RATING OF PARAPET WALL. |
| | 705.6.1. |
| | |
| | 7) STRUCTURAL SHEET S-2.1122 INDICATES THE USE OF |
| | EPICORE ER2R NOTE # 2 INDICATES 18 GAGE STEEL SUPPORTED |
| | BY CSTELLATED CELLULAR BEAMS. THE ESR-2047 REPORT ON |
| | THIS SYSTEM PROVIDES |
| | TABLES AND SPANS FOR THIS SYSTEM BEING USED WITH A |
| | POURED 4 INCH CONCRETE DECK SYSTEM. THE DETAIL SHEETS |
| | A-613 INDICATE THE USE OF ONLY RIGID FOAM AND A BUILT |
| | UP SYSTEM. HOW FAR CAN THIS STEEL DECKING SPAN WITHOUT |
| | A CONCRETE DECK, NOTE ROOFING PRODUCT APPROVALS MAY |
| | HAVE SPAN LIMITATIONS ( SPACING CENTER TO CENTER). |
| | ADDITIONAL INFORMATION REQUIRED. 106.1.2. |
| | |
| | 8) PLEASE PROVIDE SOILS REPORTS BY NORARSE & ASSOCIATES |
| | DATED 12/07/2011, FBC-B 1802.6. |
| | |
| | 9) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10)THE PRESSURES FOUND IN THE STRUCTURAL SHEETS ARE |
| | CORRECT, THESE ITEMS, PRODUCT APPROVALS CAN BE REVIEWED |
| | UNDER A REVISION WITH ASSOCIATED REVIEW AND FEES OR |
| | ONCE A CONTRACTOR HAS BEEN PICKED THEY COME IN AT THAT |
| | TIME. NOTE PERMITS THAT ARE READY FOR ISSUANCE AND THE |
| | CONTRACTOR BRINGS IN THE PRODUCT APPROVALS FOR A FIRST |
| | REVIEW MAY DELAY THE ISSUANCE OF THE PERMIT . |
| | FBC-B 1609 COMPONENTS & CLADDING, FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS GLAZED EXT DOORS, METAL EXT, |
| | OVERHEAD GARAGE STYLE & ROOF HATCH TYPE DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFING NOA |
| | 10-0125.05 SEE DECK LIMITATION # 2 DECK SPANS EVERY 5 |
| | FT. |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |