Plan Review Notes
Plan Review Notes For Permit 12020390
Permit Number 12020390
Review Stop P
Sequence Number 1
Notes
Date Text
2012-03-06 11:38:182007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE MASTER BATH FIXTURES ARE NOT PROPERLY VENTED.
 FBC P3108.2 IN HORIZONTAL WET- VENT SYSTEMS, NOT MORE
 THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION.
 PLEASE REVISE DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]