| Plan Review Notes For Permit 12020390 |
| Permit Number |
12020390 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-06 11:38:18 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE MASTER BATH FIXTURES ARE NOT PROPERLY VENTED. | | | FBC P3108.2 IN HORIZONTAL WET- VENT SYSTEMS, NOT MORE | | | THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE | | | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. | | | PLEASE REVISE DRAWINGS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|