2012-03-06 14:42:532007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SHOW COMPLIANCE WITH FBC M1602.4 FOR BALANCED RETURN
 AIR. THE TRANSFER DUCTS ARE REQUIRED TO BE 1.5 TIMES
 THE SUPPLY ENTERING THE ROOM AND UNDERCUTTING THE DOORS
 1 INCH. THE FIRST FLOOR GUEST SUITE AND SECOND FLOOR
 BEDROOMS # 2 & # 3 DO NOT COMPLY.
  
 2) SPECIFY THE SIZE OF THE TRANSFER GRILL FOR THE
 MASTER BEDROOM SUITE. FBC M1602.4(2) REQUIRES TRANSFER
 GRILLS TO USE 50 SQUARE INCHES OF GRILL AREA TO 100 CFM
 OF SUPPLY AIR FOR SIZING THROUGH THE WALL TRANSFER
 GRILLS AND UNDER CUTTING THE DOORS 1 INCH.
  
 3) REMOVE THE ARCHITECTS NAME FROM SHEET M1, UNLESS HE
 IS SIGNING AND SEALING THE DRAWINGS. FS 481
  