| 2012-03-06 14:42:53 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) SHOW COMPLIANCE WITH FBC M1602.4 FOR BALANCED RETURN | | | AIR. THE TRANSFER DUCTS ARE REQUIRED TO BE 1.5 TIMES | | | THE SUPPLY ENTERING THE ROOM AND UNDERCUTTING THE DOORS | | | 1 INCH. THE FIRST FLOOR GUEST SUITE AND SECOND FLOOR | | | BEDROOMS # 2 & # 3 DO NOT COMPLY. | | | | | | 2) SPECIFY THE SIZE OF THE TRANSFER GRILL FOR THE | | | MASTER BEDROOM SUITE. FBC M1602.4(2) REQUIRES TRANSFER | | | GRILLS TO USE 50 SQUARE INCHES OF GRILL AREA TO 100 CFM | | | OF SUPPLY AIR FOR SIZING THROUGH THE WALL TRANSFER | | | GRILLS AND UNDER CUTTING THE DOORS 1 INCH. | | | | | | 3) REMOVE THE ARCHITECTS NAME FROM SHEET M1, UNLESS HE | | | IS SIGNING AND SEALING THE DRAWINGS. FS 481 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|